Class i, division 2 guidelines – Parker Hannifin PA Series User Manual

Page 16

Advertising
background image

Chapter 2: Installing the PowerStation

Selecting a Location

PA PowerStation User Guide

2-5

Class I, Division 2 Guidelines

If you purchased a Class I, Division 2-compliant PowerStation, it is suitable

for use in Groups A, B, C, and D hazardous locations. You must follow

these guidelines in order to maintain a safe operating environment.

When performing field wiring, always use copper wire with 60C or
60/75C insulation and a tightening torque of 7.0lbs/in (0.79 N-m).

Substitution of components can impair suitability for Class I, Division 2.

The PA PowerStation is intended to use a branch circuit protection rated
20 Amps or less.

Make sure that the PA PowerStation’s “ON/OFF” switch is secured in the
“ON” position using the supplied bracket.

WARNING!

Explosion Hazard!

• Do not connect or disconnect cables unless the power has been

switched off, or the area is known to be non-hazardous. Keyboard,
mouse, and USB ports are for system setup and diagnostics only and
are not intended for permanent connection.

• Class I, Division 2 approval requires nonincendive field wiring for

Class I, Groups A, B, C, and D hazardous locations only. With a
temperature code of T5.

• Class I, Division 2 approval requires power switch restraints in

hazardous environments.

Advertising