Analog Inputs

The analog input, DEMAND, has a current range of 4 - 20 mA. It is
electrically isolated up to 500 VAC from the enclosure, 120 VDC power,
digital I/O, and serial interface. The analog interfaces are not isolated from
each other. See Figure 1-13 for a typical analog input connection.

HFG2.0

4-20mA INPUT

CONTROLLER 4-20 mA OUTPUT

+

-

DEMAND [BRN]

DEMAND RT N [WHT/BRN]

200

Ω

+

-

Figure 1-13. Typical Analog Input Connection

Analog Outputs

The analog outputs, MOTOR CURRENT and POSITION, have a current
range of 4 - 20 mA. They are electrically isolated up to 500 VAC from the
enclosure, 120 VDC power, digital I/O, and serial interface. The analog
interfaces are not isolated from each other. See Figure 1-14 for a typical
analog output connection.

CONTROL LER 4-20mA INPUT

HFG2.0 4-20mA OUTPUT

+

-

POSIT ION

[YEL]

MT R CURRENT

[BLU]

POSIT ION RT N

[W HT /YEL]

MT R CURRENT RT N [W HT /BLU]

<500

Ω

+

-

Figure 1-14. Typical Analog Output Connection

Discrete Inputs

The discrete inputs are 24 VDC ON (High) and 0 VDC OFF (Low). They
are electrically isolated up to 500 VAC. See Figure 1-15 for a typical
discrete input connection.

CONTROLLER DISCR ETE OUT PUT

HFG2.0 DISCRET E INPUT

RUN RTN

[WHT/VIO]

RESET RTN [WHTGRY]

RUN

[VIO]

RESET

[GRY]

Figure 1-15. Typical Discrete Input Command Connection