Table 5-2. hfg2.0 in-service troubleshooting chart – Hamilton Sundstrand Company Gas Fuel Metering Valve HFG2.0 User Manual

Page 63

Advertising
background image

Symptom

Probable Causes

Corrective Action

RS232 Interface Inoperative Incorrect wiring




No or low 120 VDC power
COM1 not connected
RESET or RUN command is
ON

Ensure WHITE/ORANGE/YELLOW,
WHITE/ORANGE/BLUE, WHITE/ORANGE/GREEN
wires correctly connected to valve and laptop PC.

Ensure 120 VDC Primary System Power at Valve
Check laptop/PC com port
Remove RESET or RUN command

Table 5-1. Initial Installation Troubleshooting Chart

Symptom

Probable Causes

Corrective Action

No valve feedback

No or low 120 VDC power
Self-protective valve auto shut
down

Ensure 120 VDC at valve
Upload Fault File- check for motor windings over -
temperature faults.
Check for valve contamination

FAULT alarm

Various

Upload Fault File to identify source of fault
Clear indicated fault

OVER TEMP alarm

Ambient temperature limit
exceeded

Electronics or motor winding
temperature out of range

Allow actuator to cool and re-start
Reduce ambient temperature

Check for valve contamination

FAULT and OVERTEMP
alarm

No 120 VDC Power
DSP Failure

Ensure 120 VDC at actuator
Contact factory

Table 5-2. HFG2.0 In-Service Troubleshooting Chart

For troubleshooting purposes, use Table 5-3 to verify the valve electrical
continuity integrity.

Disconnect the HFG2.0 power and digital harness connectors and use a
digital multi-meter (DMM) to check the resistance values between the
wires indicated on the table. If an open circuit is detected, send the
HFG2.0 to Precision Engine Controls Corporation for test and repair.

WARNING – Shock Hazard

Remove all power to the HFG2.0 prior to continuity check.

CH. 4: TROUBLESHOOTING THE HFG2.0

57