Hamilton Sundstrand Company Gas Fuel Metering Valve HFG2.0 User Manual

Page 62

Advertising
background image

56 HFG2.0

USER

GUIDE

Symptom

Probable Causes

Corrective Action

Valve Inoperative -
FAULT alarm

Power Wires not connected

No or low 120 VDC power

Ensure RED and GREEN wires correctly connected to
valve
Ensure 120 VDC Primary System Power at valve

Valve Inoperative -
NO FAULT alarm

No RUN or position command

Ensure VIOLET and WHITE/VIOLET wires correctly
connected to valve
Ensure 24 VDC RUN and position command at valve

Actuator moves toward
HOME then stops

Intermittent RUN command

Homing Force Too Low
No position demand

Ensure consistent 24 VDC RUN command and fuel
demand signal
Ensure position command at valve

Actuator moves toward
HOME intermittently

Intermittent RESET command

Ensure GRAY and WHITE/GRAY wires correctly
connected to Actuator
Ensure consistent 24 VDC RESET command

Actuator finds HOME then
moves to STOP position

No fuel demand signal

Ensure BROWN and WHITE/BROWN wires correctly
connected to Actuator
Ensure fuel demand > 2.0 mA at Actuator

Valve does not track fuel
demand

No fuel demand signal or RUN
command

Ensure BROWN and WHITE/BROWN wires correctly
connected to valve
Ensure valve demand > 4.1 mA at valve
Ensure RUN command present at valve

Valve does not hold
consistent position-oscillates
or dithers

Varying fuel demand signal
No or low 120 VDC power

Ensure stable fuel demand at the actuator
Ensure 120 VDC at valve

No valve feedback

Valve feedback wires not
connected
No or low 120 VDC power
Self-protective valve auto shut
down

No RUN command

Ensure YELLOW and WHITE/YELLOW wires correctly
connected
Ensure 120 VDC at valve
Upload Fault File- check for motor windings over -
temperature faults.
Check for valve contamination
Ensure RUN command present at valve

No motor current feedback

Motor current wires not
connected
No or low 120 VDC power
No RUN command

Ensure BLUE and WHITE/BLUE wires correctly
connected
Ensure 120 VDC at valve
Ensure RUN command present at valve

Valve Operative- FAULT
alarm active

FAULT wiring incorrect

Internal FAULT

Ensure ORANGE and WHITE/ORANGE wires
correctly connected to Actuator
Upload Fault File to identify source of fault

Valve Operative- OVER
TEMP alarm active

OVERTEMP wiring incorrect

Electronics or motor winding
temperature out of range
Valve jammed

Ensure BLACK and WHITE/BLACK wires correctly
connected to valve
Reduce External ambient temperature

Check for valve contamination

Valve leaks when closed

Poppet assembly fouled
Valve installed backwards

Stroke valve OPEN and clear foul at orifice
Ensure supply is connected to valve IN port