2 connections with operation display panel, Dimension, Wiring diagram – Panasonic FP2 User Manual

Page 34

Advertising
background image

FP2−CCU

RS232C Port Wiring

4 − 6

4.2

Wiring between RS232C Ports

4.2.2

Connections with Operation Display Panel

An RS232C cable (Product No. AFB85813) is available for making connections to an

operation display panel that has a D−sub 25−pin connector.
AFB85813

(Crossing cable: 9−pin external — 25−pin external)

1

6

25

13

3000

100

/118.11

3.937

1

M2.6 screws

Dimension

2

M2.6 screws

(unit: mm/in.)

Wiring diagram

D−sub 9−pin external

D−sub 25−pin external

Pin No.

PLC side

Display panel side

Signal name

(Mnemonic)

1

2

Pin No.

FG
SD
RD
RS

RI

SG

CD
ER

1
2

3

4
5
6

7

8
9

CS

1
2

3

4
5
6

7

8

20

Signal name

(Mnemonic)

FG
SD
RD
RS

DR
SG

CD
ER

CS

− The “RS” and “ER” signals of the Computer Communication Unit side

are constantly on.

− The input to the “CS” and “CD” terminals of the Computer Communica-

tion Unit side are invalid.

Tip