Interchangeability with the FP3 and Precautions

FP2−CCU

iii

Interchangeability with the FP3 and

Precautions

Hardware interchangeability

The user should be aware that there are some differences between the FP2 and FP3

Computer Communication Units.
− The DIP switch settings are different.
With the FP2 Computer Communication Unit, only the transmission speed and the

character bit can be set with the DIP switches. The settings for the parity, the stop bit

length, and whether or not the CS and CD control signals are effective are fixed as shown

in the table below.
− There is no reset switch.
The FP2 Computer Communication Unit has no reset switch.
− Connections with serial devices are made in the same way for both units.
The specifications for the RS232C interface of the FP2 Computer Communication Unit

are the same as those for the FP3.
− Two ports are provided, a “COM.1” port and a “COM.2” port.
However, the COM.1 port is restricted on the functions as below.

COM.1

COM.2

Computer link function

Available

Available

Modem connection

Not available

Available

Data transmission

Not available

Available

Hierarchy command

Not available

Available

Software interchangeability

The software is interchangeable between the FP2 and FP3 Computer Communication

Units.
− Program methods on the host side are largely the same.
There are some differences in the transmission formats, as described below.