Specifications

FP2−CCU

6 − 5

6.3

Table of MEWTOCOL−COM Error Code

6.3

Table of MEWTOCOL−COM Error Code

21 Data Error:

Situation
A data error occurred during communication.

There are three types of data errors: parity errors, framing errors, and unit

receive buffer errors.

Example of error
This occurs if the communication format between the host computer side

and the PLC side is different.

Precautions when the FP2 Computer Communication Unit is being
used

If the parity settings are different, the ERR LED lights but no error code is

returned.

ERR LED on the FP2 Computer Communication Unit
Lights

22 Overrun Error:

Situation
The CPU unit buffer is full, and no more data can be received.

Example of error
This occurs if a command being sent before a response has been

returned in cases such as commands being sent continuously from the

host side.

ERR LED on the FP2 Computer Communication Unit
Lights

24 Transmission Format Error:

Situation
There is an error in the setting of a hierarchy control command.

Example of error
This occurs if a hierarchy control command has not been notated

correctly.

ERR LED on the FP2 Computer Communication Unit
Lights