FUEL 2100 Installation and Operation Manual

NAVMAN

6

Selecting units of measure

The FUEL 2100 will indicate fuel values in Litres,
Imperial gallons or US gallons. To change the current
setting perform the following steps:

1. Power up the unit while holding down the

key.

TOTAL

FLOW

^

V

Hold down during power up

2. When the unit is on, release the

key. The

display will indicate the current display unit with:

Imperial Gallons

US Gallons

Litres

3. To select the display unit desired, use the

and

keys to change the value.

4. To exit this mode, press and hold both the

and

keys simultaneously for one second.

Press and hold to exit

Information will now be indicated in the selected
display unit.

Calibration

The fuel transducer supplied with the fuel flow meter
will provide readings at better than 5% accuracy.
Individual calibration will increase this level of
accuracy to better than 2% over a fuel flow range of
10.0 to 120 litres per hour. Use the following steps to
calibrate your fuel flow meter:

1. Reset the total log value to zero (see previous

page).

2. Use a known amount of fuel. The larger the

amount the more accurate the calibration will
be.

3. Take note of the actual volume of fuel used and

the fuel used indicated by the total log. If these
two totals are different the instrument may
require calibration.

4. Press and hold the

key while applying power

Hold down during power up

5. Release the

key. Display will flash current

total log value.

260

6. Use the

or

keys to make the display

indicate the actual volume of fuel used.

7. Press both keys simultaneously for 1 sec to

exit.

Press and hold for 1 second

The fuel flow meter is now calibrated.