Part A - DESIGN LOAD SPECIFICATIONS

A.1

Total Heat Loss _______________Btu/h

A.2

Total Heat Gain _______________Btu/h

Part B - EQUIPMENT SELECTION (Air Handler and Cooling)

AIR HANDLER:

Make: LIFEBREATH

Model: ____________

B.1

Heating Output ________________________ Btu/h

(110% - 140% of A.1)

B.2

Equipment External Static Pressure ________ ins. W.C.
(from specs)

B.3

Heating Air Flow Rate

________ cfm

B.4

Circulation Fan Speed (Heating)

________ speed

B.5

Return Air Temperature

________

o

F

B.6

Air Handler Temperature Rise

________

o

F

[B.1

÷

(1.08 x B.3)]

B.7

Supply Air Temperature

________

o

F

(B.5

+

B.6)

B.8

Water Supply Rate

________ US GPM

(from specs)

B.9

Water Supply Temperature

________

o

F

B.10 Water Temperature Drop

________

o

F

(min. 20

o

F)

[B.1

÷

(500.4 x B.8)]

B.11 Water Return Temperature

________

o

F

(B.9 - B.10)

COOLING EQUIPMENT:

B.12 Cooling Output ________ (Btu/h) ________ tons

(80% - 125% of A.2)

B.13 Manufacturers Flow Rate/Ton

________ (cfm/ton)

B.14 Cooling Air Flow Rate

________ cfm

B.15 Circulation Fan Speed (Cooling)

_______ speed

Part C - EQUIPMENT SELECTION (Water Heater)

DOMESTIC HOT WATER REQUIREMENTS:

C.1

Minimum Storage Capacity

________ USG

(from page 38, Method A)

or

C.2

Minimum First Hour Rating

________ USG

(from page 38, Method B)

SPACE HEATING REQUIREMENTS:

C.3

Minimum Effective Water
Heater Output

________ Btu/h

(B.1 x 1.2)

SELECTED WATER HEATER:

Make: ________

Model: ________

C.4

Storage Capacity

________ USG

Note: Complete C.5 and C.6 only if C.2 was completed.

C.5

Recovery

________ USG

C.6

First Hour Rating

________ USG

(.85 x (C.4

+

C.5))

(min. C.2)

C.7

Energy Factor (ef)

________

C.8

Burner Input

________ Btu/h

C.9

Recovery Efficiency

________ %

C.10 Effective Water Heater Output

________ Btu/h

(C.8 x C.9

÷

100)

(min. C.3)