Before you call for service, Gas valve error code table – Ruud PowerVent 2 AP13370-2 User Manual

Page 26

Advertising
background image

26

Before You Call For Service…

Problem

Possible Causes

What To Do

Not enough or

Water usage may have

Wait for the water heater to recover after an

no hot water

exceeded the capacity

abnormal demand.

of the water heater.

Low gas pressure.

Check gas supply pressure and manifold pressure.

The pilot burner will not light.

Check the pilot burner. If necessary, refer to the
instructions in the “Lighting The Water Heater”
section of this manual.

The gas control (thermostat)

See the “Water Temperature Setting” of The Water

may be set too low.

Heater section of this manual.

Leaking or open hot

Make sure all faucets are closed.

water faucets.

LED Status

Possible Causes

What To Do

Slow Flash

Normal Operation

No problem.

Fast Flash

Normal Operation

Wait until gas control generates a self-reset.

Call for heat.

Solid Red LED

Lockout condition.

Replace gas control.

Internal failure detected.

2 Flashes

Lockout condition.

Third failed ignition attempt. Unplug to reset control.

Ignition failure.

Contact local qualified service agent. Make sure manual
gas shut-off valve is open. If pressure is too high the
valve will not operate. Refer to “Installing the water
heater”
Clean any scale buildup from burner and pilot assembly
The spark ignitor assembly could be damaged or broken.
If so, replace assembly.
Bleed air from gas line.

3 Flashes

Lockout condition.

Contact local qualified service agent.

Switch fails to open.

Chec for blockage in the vent system.
Replace pressure switch.

4 Flashes

Lockout condition.

Contact local qualified service agent. Inspect vent pipe

Switch fails to close.

and dilution air inlet for blockage. (Refer to “Routine
Preventative Maintenance”)

Make certain proper ventilation air us supplied. (Refer to
“Combustion and Ventilation Air”)

5 Flashes

Lockout condition.

Verify electrical supply outlet polarity.

Neutral polarity failure.

6 Flashes

Lockout condition.

Replace valve.

ECO failure

CAUTION: For your safety DO NOT attempt repair of gas piping, gas control (thermostat), burners, vent connectors or
other safety devices. Refer repairs to qualified service personnel.

CAUTION: Make certain power to water heater is “OFF” before removing protective cover FOR ANY REASON.

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring error can cause improper and dangerous
operation. VERIFY PROPER OPERATION AFTER SERVICING.