Troubleshooting guidelines – Reliance Water Heaters 317775-000 User Manual

Page 37

Advertising
background image

37

trouBleshootInG GuIdelInes

trouBle shootInG

Please check guidelines below. For your safety, water heater service should be performed only by a qualified service technician.

Read the GENERAL SAFETY INFORMATION section first.

INTELLI-VENT TROUBLESHOOTING CHART - USER CONTROL

PROBLEM

SOLUTION

15

# LED STATUS

B C D E F

1. Turn off power to the water heater.
2. Unplug the ignitor assembly plug from the control. Check

the resistance of the black resistor wire between pins

3 & 4 with an ohm meter. 2.1 If the reading taken is more

than 100,000 (50,000 for data code before 0616; 70,000

for data code 0617 through 0709) ohms replace the ignitor

assembly. 2.2 If the reading taken is less than 100,000

(50,000 for data code before 0616; 70,000 for data code

0617 through 0709) ohms replace Intelli-Vent™ control.

The self-diagnostic test determined resistance

of the black resistor wire on ignitor assembly

plug is not within tolerance.

1. Ensure air pressure switch hose is not kinked or clogged;

ensure the blower housing is clear of any condensation.

2. Check vent temperature limit switch - if it is determined

that the vent temperature limit switch is opening its

contacts at normal operating temperatures during heating

cycle - replace the vent temperature limit switch.

3. Ensure water heater is not over-firing. 3.1 Check burner

orifice size and ensure the correct orifice is installed;

replace as necessary. 3.2 Check manifold gas pressure

and ensure it is within 0.3” W.C. (75 Pa) of listed rating on

Intelli-Vent™ control valve. Manifold gas pressure is

non-adjustable, if manifold gas pressure is off by more

than 0.3” W.C. (75 Pa), replace the Intelli-Vent™ control.

4. Ensure condensate lines are not obstructed. Check and

clear all condensate lines including the floor condensate

drain line.

Air pressure switch circuit is opening

repeatedly during one heating cycle. May be

caused by air pressure switch and/or the vent

temperature limit switch (these two switches

are wired together in a “series” circuit).

16

B C D E F

WA

TE

R

HE

AT

ER

CONTRO

L