COMBUSTION AND VENTILATION AIR SUPPLY
CAUTION:
Combustion air must not be contaminated by corrosive chemical fumes which can damage the heater
and void the warranty.

IMPORTANT: Adequate air must be provided for proper combustion and ventilation of the surrounding area. An
inadequate supply of combustion air will result in incomplete combustion and eventual sooting of the heater.
Insufficient ventilation will cause excessive heat and rapid deterioration of electronic and electrical components.
Equipment rooms should be provided with TWO permanent air supply openings directly connected to outside air.
Each opening must have a minimum FREE area of one square inch per 4000 BTU per hour input of the total input
rating of all equipment in the room. Local codes or authorities having jurisdiction should be consulted for the following
table.
RECOMMENDED MINIMUM AIR OPENINGS

NET

NET

NET

BOILER

FREE

BOILER

FREE

BOILER

FREE

SIZE

AREA

SIZE

AREA

SIZE

AREA

136

34

512

128

1125

282

181

47

627

157

1223

306

264

66

726

182

1337

335

331

84

825

207

1467

367

399

100

962

241

1630

408

All area shown in square inches

1826

457

For other conditions refer to the latest edition of the National Fuel Gas Code ANSI Z 223.1. Net free area, sq. in.
requires data from louver manufacturer based on resistance of screening, if provided.

OUTDOOR INSTALLATIONS
MODEL 136

Step 1: Remove the front (4) screws
Step 2: Line up outdoor top vent opening over heater

vent opening.

Step 3: Lower outdoor top onto unit lining up slots in the

outdoor top with screws holes in jacket top.

Step 4: Reinstall (5) screw to secure jacket top and

outdoor top to unit.

Fig. # 8114

10

MODEL 181-399

VENT TERMINAL (Outdoor) Stackless Top Installation

1. Insert tabs into keyhole (4 places).

Pagoda Top
(Shipped
Loose with
Heater)

Advertising