COMBUSTIBLE CONSTRUCTION CLEARANCES
The water heater should be positioned to provide the minimum clearances from combustible surfaces and to
provide sufficient space for servicing the unit as follows.

MINIMUM CLEARANCES:

PROTECTED SURFACES

Clearances to surfaces installed
in rooms which are large (2) in
comparison with size of heater.

Rear

12"

9

6

4

6

4

4

4

4

Left Side

12"

9

6

4

6

4

4

4

4

136

Right Side

6"

5

3

3

6

2

3

3

3

Indoor Top

42"

42

42

42

42

42

42

42

42

Rear

12"

9

6

4

6

4

4

4

4

Left Side

12"

9

6

4

6

4

4

4

4

181-399 Right Side

12"

9

6

4

6

4

4

4

4

Indoor Top

39"

39

39

39

39

39

39

39

39

Outdoor Top(1)

Rear

12

9

6

4

6

4

4

4

4

Left Side

18

12

9

6

6

6

6

6

6

512-825 Right Side

6

5

3

3

6

2

3

3

3

Indoor Top

36

36

36

36

36

36

36

36

36

Outdoor Top

(1)

Rear

24

16

12

8

8

8

8

8

8

Left Side

24

16

12

8

8

8

8

8

8

926-1826 Right Side

24

16

12

8

8

8

8

8

8

Indoor Top

24

24

24

24

24

24

24

24

24

Outdoor Top

(1)

(1) Unobstructed.
(2) Large rooms are defined as having a volume at least 16 times the total volume of the heater.
(3) Installation clearances for heaters in rooms not large in comparison with the heater size shall be as listed

under combustible surfaces and shall not be reduced by the protection methods.

SERVICING CLEARANCES:

24" in front of heater for removal of burner tray.
18" on side opposite water connection for deliming of Heat Exchanger on
Models 181-1826 only.

Combustible Surfaces

(a) 3 1/2-in. thick masonry wall with- out ventilated air space

(b) 1/2-in. insulation board over 1-in. glass fiber or mineral wool batts

(c) 0.024 sheet metal over 1-in. glass fiber or mineral wool batts reinforced with wire on rear face with ventilated air space

(d) 3 1/2-in. thick masonry wall with venti-

lated air space

(e) 0.024 sheet metal with ventilated air

space

(f) 1/2-in. thick insulation board with ventilated air space

(g) 0.024 sheet metal with ventilated air space over 0.024 metal with ventilated air space

(h) 1-in. glass fiber or mineral wool batts sandwiched between two sheets 0.024 sheet metal with ventilated air space