HEATER INSTALLATION

Critical Hanger Placement

Hanger

Side View

Must Be Within 4" (10 cm)

Front View

S Hooks

Reflector

Hanger

45° Angle

* Allows for thermal expansion of system

Typical Suspension Details

Rod (3/8")

Beam Clamp

Concrete Beam

Wood Beam

Washers

Locknut

Screw Hook

(3/8")

24" min.*

(61 cm)

“X”*

Anchor

“S” Hooks

Chain size

3/16" minimum

Turnbuckle

Not Included

Description

Par t Number

S-Hook

91907302

Tube/Reflector Hanger

03090100

Total Str aight Length (both si des) or Length from U-Tube to U-Tube

i n a Double "U" Layout

Typical Expansion

Each Si de

Minimum “X” Length

0’ - 50’

±1” (3 cm)

12” (31 cm)

51’ - 60’

±2” (5 cm)

18” (46 cm)

61’ - 80’

±3” (8 cm)

24” (61 cm)

81’ - 100’

±4” (10 cm)

30" (76 cm)

101’ - 120’

±5” (13 cm)

36" (91 cm)

121’ - 140’

±6” (15 cm)

42" (107 cm)

141’ - 160’

±7” (18 cm)

48" (122 cm)

If the installation requires a shorter suspension length than the minimum listed, the suspension
length may be reduced by 6" (16 cm). In this case tube clamps MUST be used at the two farthest
hangers on each side of the burner. See Page 8, Figure .