SECTION 7: H

EATER

I

NSTALLATION

15

SECTION 7: HEATER INSTALLATION

To ensure your safety and comply with the terms of
the warranty, all units must be installed in
accordance with these instructions.

The gas or the electrical supply lines must not be
used to support the heater.

Do not locate the gas or electric supply lines directly
over the path of the flue products from the heater.
The heater must be installed in a location that is
readily accessible for servicing.
The heaters must be installed in accordance with
clearances to combustibles as indicated on the rating
plate and in this instruction manual.
The minimum and maximum gas inlet pressures
must be maintained as indicated on the rating plate.
Typical installation configurations are shown in
Figure 12.
Expansion and contraction of the tube dictates that
the minimum suspension lengths in the table on
Figure 12 be maintained.

FIGURE 12: Critical Hanger Placement

WARNING

Suspension Hazard

Hang heater with materials with a

minimum working load of 75 lbs

(33 kg).

Failure of the supports can result

in death, injury or property

damage.

Side View Towards Pump

Typical Suspension Details

Turnbuckle

Rod 3/8"

Beam Clamp

Concrete Beam

Wood Beam

Washers

Locknut

Screw Hook

3/8"

24" min.

(61 cm)

"X" (See Table)

Locknut

(Typical)

Anchor

Hanger

Front View

S-Hook

Turnbuckle

Reflector

7'6" (2.3 m)

Chain size

3/16" minimum

Description

Part Number

Turnbuckle

91903201

S-Hook

91907302

Tube/Reflector Hanger

03090100

Run Length

Typical Expansion

Minimum “X” Length

50' (15 m)

±1" (3 cm)

12" (30 cm)

100' (31 m)

±2" (5 cm)

24" (61 cm)

150' (46 m)

±3" (8 cm)

36" (91 cm)

200' (61 m)

±4" (10 cm)

46" (122 cm)

250' (76 m)

±5" (13 cm)

57" (145 cm)