56 troubleshooting flow chart, Control panel ios manuals, Pump ios manuals – Roberts Gorden CoRayVac CRV-B-9 User Manual

Page 62

Advertising
background image

CRV-S

ERIES

I

NSTALLATION

, O

PERATION

AND

S

ERVICE

M

ANUAL

56

Troubleshooting Flow Chart

No

Replace filters as necessar

y.

Replace the electrodes.

Adjust the gap or

replace the electrode.

Ignition module may have failed. Replace module.

Electrode gap should be 1/8". Is the gap too small?

No

Ye

s

Inspect the electrodes on the affected burners. Are they

burned or damaged?

No

Ye

s

Couplings may be installed improperly

. Lined couplings

should be used for tailpipe.

Refer to control panel manuals listed below

.

Make sure that all

thermostats or internal sensors are satisfied.

Ye

s

Do burners shut off after the

call for heat is satisfied?

Ye

s

No

Check for blockage in the outside air supply or for

leaks in the system.

Replace filters as necessar

y.

No

Ye

s

Are the filters on the

burners dirty?

Consult wiring instructions in pump manuals listed below

for reversal instructions.

Is the rotation of the pump motor correct?

Ye

s

No

Adjust system for proper vacuum at the end vent.

Is the vacuum setting

too low?

No

Ye

s

Is the flame low?

No

Ye

s

No

Ye

s

Are the filters on the

burners dirty?

Ye

s

No

Is the rotation of the pump motor correct?

Adjust system for proper vacuum at the end vent.

Follow burner check procedure given above.

No

Ye

s

Are there any "dead" burners in a branch?

Is the vacuum setting

too low?

No

Ye

s

Is the system leaking water?

No

Ye

s

Do the burners lockout

intermittently?

No

Ye

s

Make sure that all

thermostats or internal sensors are satisfied.

Ye

s

Does the pump shut down after a 2 minute post-purge

period?

Ye

s

No

TROUBLESHOOT ENDS. If problems persist, contact

your

ROBER

TS

GORDON

®

Independent

Distributor

.

Refer to control panel manuals listed below

.

Contact

Roberts-Gordon at www

.rg-inc.com

Consult wiring instructions in pump manuals listed below

for reversal instructions.

Control Panel IOS Manuals:

- System Control P/N: 10091601NA - ROBER

TS GORDON

®

UL

TRA

VAC™ P/N: 10081601NA

- For systems with no control panel, refer to appropriate control manufacturers instructions.

Pump IOS Manuals:

- EP-100 P/N: 127201NA - EP-200 P/N: 127200NA - EP-300 P/N: 127202NA