30

Step 8.9 Classic Cast-Iron Components

WARNING

Suspension Hazard

Hang heater with materials

with a minimum working load

of 750 lbs. (340 kg).
Use special tube and reflector

hangers when suspending

the schedule 40 steel pipe

system.
Schedule 40 steel pipe is

heavy and will fall

if not supported properly.
Distance between supports

must be 7' (2.13 m) or less.
Failure to follow these

instructions can result in

death, injury or property

damage.

Schedule 40 Steel Pipe

Cast-Iron Combustion

Chamber

Cast-Iron Adapter

End Vent Plate for

End Burner Only

Cast-Iron Adapter

Coupling

4" Tube

7' (2.13 m) Maximum

Cast-Iron Combustion Chamber

with Schedule 40 Steel Pipe

The total weight of each burner and

combustion chamber is 40.25 lbs (18 kg).

4" Schedule 40 pipe weighs 10.9 lbs.

(5 kg) per foot.

Cast-Iron Combustion Chamber with

Standard 4" O.D. Infrared Tubing

The total weight of each burner and

combustion chamber is 40.25 lbs (18 kg).

4" O.D. 16 Ga. tubing weighs 2.8 lbs.

(1.3 kg) per foot.

ROBERTS-GORDON

®

End Vent Plate for

End Burner Only

End Vent

Clips

Special Tube and Reflector Hanger

ROBERTS-GORDON

®

End Vent

Clips

CORAYVAC

®

Classic

Turnbuckle

Hang cast-iron combustion chamber with a turnbuckle

(spring clips will not fit around cast-iron hanging loop).

Description

Part Number

Special Tube & Reflector Hanger

02790300

Turnbuckle

91903201

Cast-Iron Combustion Chamber

02721200-1P

Cast-Iron Adapter

02722100

Coupling

01312700