9.3 Horizontal Venting 4" (10 cm) Pipe

FIGURE 16: EP-100 Horizontal Venting Configurations

25' (8 m) and 3 Elbows Maximum

50' (15 m) and 3 Elbows Maximum

Bird

Screen

4" (10 cm) Single Wall Pipe

5" (12.5 cm) Single Wall Pipe

Vent Terminal

Tjernlund VH1-4

Vent Terminal

Tjernlund VH1-6

Approved Thimbles

5" to 4" Reducer

(12.5 cm to 10 cm)

6" to 5" Reducer

(15 cm to 12.5 cm)

18" (46 cm) Minimum -

40" (102 cm) Maximum

18" (46 cm) Minimum -

40" (102 cm) Maximum

Pitch single wall pipe

downward away from pump

1/4" (6 mm) for every 10' (3 m).

4" (10 cm)

Band Clamp

Part Number

Description

Part Number

Description

01330203

Tee, 4" (10 cm) Aluminized

90505600

Wall Thimble, 4" (10 cm)

01331900

Damper Coupling, 4" (10 cm)

91409403

Tube, Aluminized 4" (10 cm) dia. 10' (3 m)

01335801

Elbow, 4" (10 cm) Aluminized 90°

91412800

Flexible Boot, 4" (10 cm)

01365400

Bird Screen, 4" (10 cm)

91901300

Boot Clamp, 4" (10 cm)

02537801-1P

Vent Terminal (Non-Combustible Wall)

Not Supplied

Tube, Aluminized 5" (12.7 cm) dia. 10' (3 m)

02718851

Drain Cap, 4" (10 cm)

Not Supplied

Tube Adapter, 5" (12.7 cm) dia. x 4" (10 cm) dia.

90502100

Vent Terminal, 4" (10 cm) (Combustible Wall)

Not Supplied

Tube Adapter, 6" (15.2 cm) dia. x 5" (12.7 cm) dia.

90502101

Vent Terminal, 6" (15 cm) (Combustible Wall)