SECTION 4: T

YPICAL

E

XTERNAL

W

IRING

D

IAGRAMS

7

SECTION 4: TYPICAL EXTERNAL WIRING
DIAGRAMS

4.1 EP-100 or EP-201 120 V 1 Ø Pump External
Wiring Diagram

The external wiring diagram above shows the con-
nections for four zones of system burners. System
burners can be either CORAYVAC

®

or VANTAGE

®

NP

(multiburner only).

The zones are connected to a single pump, unless
zone 3 and/or zone 4 are selected to function with
the optional pump 2. The external wiring diagram
below shows connection to an EP-100 or EP-201 120
V 1 Ø pump.

4.1.1 External Wiring Connection Details

The cable used for all the wiring must be rated for
line voltage up to 600 Vac.

The low voltage circuit conforms with Class 2 separa-
tion of circuit requirements. National Electrical Codes

®

for wiring class 2 low voltage circuits must be followed.

FIGURE 5: External Wiring Diagram ROBERTS GORDON

®

EP-100 and EP-201 120 V 1 Ø Pump

DANGER

Electrical Shock Hazard

Disconnect electric before service or
maintenance.

More than one disconnect switch may be
required to disconnect electric to the unit.

Failure to follow these instructions can result
in death or electrical shock.

System Control

R

R

R

R

PS 2

PS 1

24 VAC
COM

24 VAC
COM

PS 1

PS 2

W

W

W

W

24 VAC

120 V
1 Ø
60 Hz

Ground

G

L

N

120 V
1 Ø
60 Hz

PUMP 2

PUMP 1

POWER
SUPPLY

N L

Z1

Z2

Z3

Z4

N

N

N

N

L

L

L

L

All burners must be
connected to Ground
(Not shown)

Zone 1 Zone 2 Zone 3 Zone 4

EP-100 or

EP-201 Pump

N L

EP-100 or

EP-201 Pump

L

N

TWO PUMP SYSTEM (optional)
Pump 1 may be used for all zones.
Pump 2 may be used to control
zone 3 and/or zone 4.

Low voltage thermostats

located in heated zone

Zone

1

Zone

2

Zone

4

Zone

3

Pressure
switch
located at
Pump 2

Pressure
switch
located at
Pump 1