Caution, System control, Ground – Roberts Gorden System Control HP 208 V 3 User Manual

Page 14: 8figure 6: external wiring diagram roberts gordon, Or van- tage

Advertising
background image

S

YSTEM

C

ONTROL

I

NSTALLATION

, O

PERATION

AND

S

ERVICE

M

ANUAL

8

FIGURE 6: External Wiring Diagram ROBERTS GORDON

®

EP-100, EP-201 or EP-301, 230 V 1 Ø Pump

4.2 EP-201 or EP-301 230 V 1 Ø External Wiring
Diagram

The external wiring diagram above shows the
connections for four zones of system burners.
System burners can be either CORAYVAC

®

or VAN-

TAGE

®

NP (multiburner only).

The zones are connected to a single pump, unless
zone 3 and/or zone 4 are selected to function with
the optional pump 2. The external wiring diagram
above shows connection to an EP 301 or EP-201 1 Ø

pump.

4.2.1 External Wiring Connection Details

The cable used for all the wiring must be rated for
line voltage up to 600 Vac.

The low voltage circuit conforms with Class 2 separa-
tion of circuit requirements. National Electrical Codes

®

for wiring class 2 low voltage circuits must be followed.

System Control

R

R

R

R

PS 2

PS 1

24 VAC
COM

24 VAC
COM

PS 1

PS 2

W

W

W

W

24 VAC

120 V
1 Ø
60 Hz

Ground

G

L

N

120 V
1 Ø
60 Hz

PUMP 2

PUMP 1

POWER
SUPPLY

N L

Z1

Z2

Z3

Z4

N

N

N

N

L

L

L

L

All burners must be
connected to Ground
(Not shown)

Zone 1 Zone 2 Zone 3 Zone 4

EP-100,

EP-201 or

EP-301 Pump

N L

L

N

TWO PUMP SYSTEM (optional)
Pump 1 may be used for all zones.
Pump 2 may be used to control zone 3
and/or zone 4. Refer to Pump 1 for configuration.

Low voltage thermostats

located in heated zone

Zone

1

Zone

2

Zone

4

Zone

3

Pressure
switch
located at
pump 2

Pressure
switch
located at
pump 1

208 - 230 V
1 Ø
60 Hz

L2

L1

M

1

5

3

2

6

4

Individual supply for
pump rated for total full
load current. See Section
2.3 for details.

EP-100, EP-201 or

EP-301 Pump

The power supply for the
pump must be separate
from the controller supply

Motor Contactors
P/N 10050011
P/N 10050012

CAUTION

Product Damage Hazard

Do not directly connect control relay terminals
to pump motor.

Failure to follow these instructions can result
in product damage.