SECTION 5: T

ROUBLESHOOTING

13

FIGURE 9: System Control Troubleshooting Chart

Contact

Roberts-Gordon LLC

at www.rg-inc.com.

Contact

Roberts-Gordon LLC

at www.rg-inc.com.

Contact

Roberts-Gordon LLC

at www.rg-inc.com.

Contact

Roberts-Gordon LLC

at www.rg-inc.com.

Troubleshoot ends.

Contact

Roberts-Gordon LLC

at www.rg-inc.com.

Does the pump turn off

following post purge period?

No

Yes

Do the burners turn off

when the thermostat is

satisfied?

No

Yes

Rectify.

Do the burners in the

zone come on?

No

Has the system been

commissioned?

No

Yes

Is external wiring to the

zone OK?

Yes

No

Refer to burner trouble-

shooting in either the

CORAYVAC

®

or

VANTAGE

®

NP

Installation, Operation and

Service Manuals.

Refer to the burner start up

instructions in either the CORAYVAC

®

or VANTAGE

®

NP Installation, Operation

and Service Manuals.

Do the incorrect zone

lights or all zone

lights come on?

Yes

No

Are the zone thermostats

wired correctly?

No

Yes

Rectify.

Is external wiring to the

pressure switch OK?

Yes

No

Rectify.

Rectify.

Yes

No

Is the correct contactor

selected for the

pump?

Adjust thermostat set

point to call for heat.

Does the pump

come on?

No

Yes

Does the zone light

come on?

Yes

No

No

Yes

Yes

No

Is external wiring to the

pump OK?

Fit the correct contactor.

Is the thermostat connected
to the correct terminal at the

system control.

Yes

Replace fuse with

P/N 10000212.

Is the line power

indicator on?

Check the power supply

to the system control

panel. Is it on?

Yes

Yes

Check the 250mA

fuse. Is it OK?

Yes

No

No

Rectify power supply

problem.

No

No

Does the pressure switch

light come on?

Refer to burner trouble-

shooting in either the

CORAYVAC

®

or

VANTAGE

®

NP

Installation, Operation and

Service Manuals.

Refer to burner trouble-

shooting in either the

CORAYVAC

®

or

VANTAGE

®

NP

Installation, Operation and

Service Manuals.

Turn off power and correct

wiring.

Yes

Contact

Roberts-Gordon LLC

at www.rg-inc.com.

If control is not working properly, disconnect power to control and check for signs
of physical damage to the front and back of the circuit board, water damage (cor-
rosion) or scorching. If damage is found, identify and rectify source of
damage. Replace circuit board (P/N 10090101), if it has permanent damage.