Ground the switch – Rockwell Tools STRATIX 8000 ETHERNET 1783-MS10T User Manual

Page 38

Advertising
background image

38

Publication 1783-UM002C-EN-P - April 2009

Chapter 2

Ground the Switch

Follow these steps to connect the switch to a protective ground.

1.

Use a standard Phillips screwdriver or a ratcheting-torque screwdriver
with a Phillips head to remove the ground screw from the front panel of
the switch.

2.

Store the ground screw for later use.

3.

If your ground wire is insulated, use a wire stripping tool to strip the 5.3
mm

2

(10 AWG) ground wire to 12.7 mm (0.5 in.) ± 0.5 mm (0.02 in.).

4.

Insert the ground wire into the ring terminal lug.

ATTENTION

For proper grounding, you must always connect the power
supply functional-ground screw when connecting the power
supply. You must provide an acceptable grounding path for each
device in your application. For more information on proper
grounding guidelines, refer to publication

1770-4.1

, Industrial

Automation Wiring and Grounding Guidelines.

ATTENTION

You must use the external grounding screw on the front of the

switch to ground the switch. Use a 5.3 mm

2

(10 AWG) ground

wire.

31789-M

12.7 mm (0.5 in.)