How to Reset and Program Thermocouple Type (or RTD)

How to Reset and Program Thermocouple Type (or RTD)


A DPS3301-TC that is calibrated for a J, K, T, or E type thermocouple or an RTD model may be
programmed for a specific thermocouple, or RTD (385/392) type, by going into SETUP mode (Look under
‘SETUP’). Alternately, a thermocouple/RTD may be selected by turning On

A DPS3301-TC that is calibrated for a J, K, T, or E type thermocouple or an RTD model may be
programmed for a specific thermocouple, or RTD (385/392) type, by going into SETUP mode (Look under
‘SETUP’). Alternately, a thermocouple/RTD may be selected by turning On power to the unit while holding
in
the appropriate key (see Figure 1). This procedure also clears the memory and programs factory defalult
values for limits, rate timebase etc. Therefore, after performing Power-up reset, various parameters such as
limits, rate time base etc., must be re-programmed to a desired value. However, if done in SETUP mode, no
programmed parameters such as limits, Timers etc. are erased from the memory. It is recommended that
thermocouple (RTD) selection be done in SETUP. Power-up reset should be performed if it is suspected that
program memory may have been corrupted due to power surge, noise on electrical lines etc.

FIGURE 1. Thermocouple/RTD Selection Keys

KEY Input Type Selected

HI/LO

J (R, S or B , RTD 385)

Thermistor

C/F

K (RTD 392)

ALARM T
TIMER

E



RESET

Memory cleared – no

factory default values

. programmed.



NOTE: All keys, except RESET, clear
memory and program necessary factory
default values. RESET key clears memory
only and programs no default values.
However, previous thermocouple type is
retained.










DISPLAY MODES

E t/c

Memory Clear only

T t/c

K t/c, RTD392,

Thermistor

J (R, S or B) t/c,

RTD385


The DPS3301 can be programmed to display in any one of the following modes:

Mode

Display

Description


PROCESS

PrOCESS

Displays process value.


SETPOINT DEVIATION

SP. DEVN

Displays setpoint deviaition.


INSTANTANEOUS RATE

In. rAtE

Displays Instantaneous rate value.


PROCESS HIGH

Pr. HIGH

Displays process’ highest reading


PROCESS LOW

Pr. LO

Displays process’ lowest reading


ELAPSED TIME

ELPSd. T

Displays elapsed time.


TIMER 1 COUNT DOWN

tr1. Cnt

Display Timer 1 count down value


TIMER 2 COUNT DOWN

tr1. Cnt

Display Timer 2 count down value


SCAN

SCAn

Scans through all the above parameters