Mantel Requirements

Combustible Mantels

Use the table below to determine the maximum mantel depth allowed. The mantel depth (measured from the

face of the fireplace) must fall in the shaded portion of the table.

Any material that protrudes more than 3/4” (19mm) from the non-combustible facing is considered a mantel

and must meet the mantel requirements.

36-3/4"

933mm

a

b

Maximum Mantel Depth (b)

Mantel

Height

Above

Face (a)

0”

(25mm) 1"

(51mm) 2"

(203mm) 8"

(178mm) 7"

(152mm) 6"

(127mm) 5"
(102mm) 4"

(76mm) 3"

(229mm) 9"

0”

(254mm) 10"

(279mm) 11"

(305mm) 12"

(330mm) 13"

(356mm) 14"

(381mm) 15"

(406mm) 16"

(432mm) 17"

(457mm) 18+"

Base of the Fireplace

Combustible mantel columns (legs) that protrude
more than 3/4" (0.75mm) from the glass frame
must meet the sidewall clearance. If they
protrude 3/4" (0.75mm) or less, they must meet
the facing clearance 2-1/4" (57mm) from the
glass frame.

Non-combustible mantel columns do not have a
minimum clearance.

Combustible Mantel

1" (25mm)

2" (51mm)

8" (203mm)

7" (178mm)

6" (152mm)

5" (127mm)

4" (102mm)

3" (76mm)

9" (229mm)

10" (254mm)

11" (279mm)

12" (305mm)

Examples:

- If you wish to have an 8” (203mm) deep mantel, it must be at least 6-3/4” (171mm) above the fireplace face (44-3/4”, 1137mm above the base).

- If you wish to have a mantel 8” (203mm) above the fireplace face, it must be no deeper than 9” (229mm).

Non-Combustible Mantels

Non-combustible mantels must meet the clearances listed for combustible mantels. However, if you do wish to

reduce the clearances by using a non-combustible mantel, the following requirements must be met:

Non-combustible mantel

and facing must extend

from the top of the

appliance to the top

surface of the mantel.

A non-combustible

header must be used

(metal stud).

SIDE OF FIREPLACE

Drywall

Non-Combustible Mantel

Non-Combustible Framing (metal studs)

must be used for the header.

Non-Combustible Facing