Orbit Manufacturing Rokonet ORBIT-6 RP-206 User Manual

Page 17

Advertising
background image

Installer Manual

17

Locations: 14-21

Zone 1-8: (1

st

Digit): Type

Default:

1

st

Digit

Zone Type and Comments

0

Not Used
All unused zones should be given this designation. It is also used to disable a zone

1

24-Hour
A violation of such a zone will always cause an instant intrusion alarm, regardless of
the system’s armed/disarmed state

2

Instant (Intrusion)
Causes an immediate intrusion alarm if violated when the system is in arm state. Entry
Delay.

3

Entry/Exit Delay
If violated, a zone with this designation will not cause an intrusion alarm during the
Entry and Exit Delay periods

4

Exit (OPEN)/Entry
Such a zone behaves as described above in Entry/Exit Delay, except that if faulted at
the time the system is armed, it will be bypassed and NOT prevent system arming.
To avoid an intrusion alarm, however, it must be secured before the expiration of the
Exit Delay period (Location 11).

5

Entry Follower
A zone(s) given this designation will cause an immediate intrusion alarm when violated
unless an Entry/Exit zone was violated first if so, an Entry Follower zone(s) will remain
bypassed until the end of the Entry Delay period

6

Interior + Entry Delay Follower
If the system is armed to

AWAY (ARM) mode: this type of zone behaves like the Entry

Follower, described above
If the system is armed to the

STAY mode: this type of zone will be bypassed

Important Note: When arming with "STAY" mode it is possible for the user to eliminate
the entry delay period by pressing the (STAY) key twice in succession when arming
the system.

7

Fire Zone
Intended for smoke or other types of fire detectors. If violated, will cause an immediate
fire alarm. Only Zone 5 can be programmed as a fire zone. A fault in the wiring of any
fire zone, if supervised, will cause a fire alarm, manifested by a rapid flushing of the
keypads' Fire LED.

8

Tamper Zone
Only Zone 6 can be a Tamper Zone. It operates the same as 24 hours Zone, but this
type has a special reporting code.

9

Panic Zone
If violated an immediate panic alarm will be announced.

A

Key-switch Zone - Instant
If desired for system arming and disarming an external SPST spring - loaded,
normally open, momentary type key switch can be added. The key switch permits an
instant arm and disarming of the system after tripping.

B

Key-switch Zone - Delayed
Such a zone behaves as described above in "key switch zone instant", except when
arming the system an exit delay will follow.

**C

Latch-Key-switch Zone – Instant: If desired for system arming/disarming, connect
an external SPST latching type (non-momentary) key-switch to any zone terminals,
given this designation.

**D

Latch-Key-switch Zone – Delayed: Such a zone behaves as described above in
"latched key switch zone instant", except when arming the system an exit delay will
follow.

** New in Version 1.3