TOA Electronics SSDV-3328 User Manual

Page 18

Advertising
background image

18

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

H1

V

V1

H

V

H1

H

V1

u

Ceiling

Firestop / Spacer

(SV4.5VF)

u

Ceiling

Firestop / Spacer

(SV4.5VF)

v

Wall Firestop/

Spacer (SV4.5HF)

v

Wall Firestop/

Spacer (SV4.5HF)

u

Ceiling

Firestop / Spacer

(SV4.5VF)

Example: If 20 feet total (H+H

1

)

horizontal vent run is needed,

then 4 feet minimum of (V) verti-

cal vent will be required.

This table shows a 1(V) to 5(H)

ratio. For every 1 foot of (V)

vertical, you are allowed 5 feet

of (H+H

1

) horizontal run up to

a maximum total horizontal run

of 20 feet.

An elbow is acceptable as 1 foot

of vertical rise except where

an elbow is the only vertical

component in the system. See

Figure 35.

Table D

H +

H

1

Maximum

V Minimum

feet

(meter)

feet

(meter)

5

(1.524)

Elbow Only

5

(1.524)

1

(0.305)

10

(3.048)

2

(0.610)

15

(4.572)

3

(0.914)

20

(6.096)

4

(1.219)

H + H

1

= 20 feet (6.096 m) Max.

V + V

1

+ H + H

1

= 40 ft. (12.192 m) Max.

Table C

H

+H

1

Maximum

H

Maximum

V Minimum

feet

(meter)

feet

(meter)

feet

(meter)

5

(1.524)

2

(0.610)

1

(0.305)

10

(3.048)

4

(1.219)

2

(0.610)

15

(4.572)

6

(1.829)

3

(0.914)

20

(6.096)

8

(2.438)

4

(1.219)

V + V1 + H + H1 = 40 feet (12.2 m) Max

H = 8 feet (2.438 meters) Max.

H + H1 = 20 feet (6.096 meters) Max.

Example: If 20 feet total (H+H

1

) horizontal vent run is needed,

then 4 feet minimum of (V) vertical vent will be required.
This table shows a 1(V) to 5(H) ratio. For every 1 foot of (V)

vertical, you are allowed 5 feet of (H+H

1

) horizontal run up to a

maximum total horizontal run of 20 feet.

u

When using Secure Flex, use Firestop / Spacer SF4.5VF

v

When using Secure Flex, use Firestop / Spacer SF4.5HF

u

When using Secure Flex, use Firestop / Spacer SF4.5VF

v

When using Secure Flex, use Firestop / Spacer SF4.5HF

Figure 29 - Rear Vent - THREE ELBOWS

Figure 30 - Top Vent - THREE ELBOWS

VERTICAL VENT FIGURES/TABLES

(CONTINUED)

HORIZONTAL (OUTSIDE WALL)

TERMINATION SYSTEM

Figure 31, and Figures 34 to 40 on Pages

21 to 23 and their associated Horizontal Vent

Table illustrate the various horizontal venting

configurations that are possible for use with

these appliances. Secure Vent pipe applications

are shown in these Figures; Secure Flex pipe

may also be used. A Horizontal Vent Table sum-

marizes each system’s minimum and maximum

vertical and horizontal length values that can be

used to design and install the vent components

in a variety of applications.

Both of these horizontal vent systems terminate

through an outside wall. Building Codes limit or

prohibit terminating in specific areas. Refer to

Figure 7 on Page 8 for location guidelines.

Secure Vent SV4.5 direct vent system compo-

nents are unitized concentric pipe components

featuring positive twist lock connection, (refer

to Figure 20 on Page 15). All of the appli-

ances covered in this document are fitted with

collars having locking inclined channels. The

dimpled end of the vent components fit over

the appliance collar to create the positive twist

lock connection.

A. Plan the vent run -

Analyze the vent routing and determine the

types and quantities of sections required

4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2"

(572 mm), 34-1/2" (876 mm) and 46-1/2" (1181

mm) net section lengths are available. Plan the

vent lengths so that a joint does not occur at the

intersection of ceiling or roof joists. Make allow-

ances for elbows as indicated in Figure 22.
Maintain a minimum 1" (25 mm) clearance to

combustibles on the vertical sections. Clear-

ances for the horizontal runs are; 3" (76 mm)

on top, 1" (25 mm) on sides, and 1" (25 mm)

at the bottom.