Warning – TOA Electronics SSDV-3328 User Manual

Page 21

Advertising
background image

21

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

H

H = 28 in. (711 mm) Maximum.

7 in. (178 mm)

When using Secure Flex,

use Firestop/Spacer

SF4.5HF

Wall Firestop/Spacer

(SV4.5HF)

H

V

Wall Firestop/Spacer

(SV4.5HF)

When using Secure Flex,

use Firestop/Spacer

SF4.5VF.

Ceiling

Firestop/Spacer

(SV4.5VF)

When using Secure Flex,

use Firestop/Spacer

SF4.5HF.

Figure 35

- Top Vent -

ONE 90 DEGREE ELBOW - ELBOW CONNECTION AT APPLIANCE

Figure 34

- Rear Vent - NO ELBOWS - Square Horizontal

Termination (SV4.5HT-2)

H

Wall

Firestop/Spacer

(SV4.5HF)

V

When using Secure Flex,

use Firestop/Spacer

SF4.5HF

Notes:

• Secure Vent components (rigid vent pipe and terminal) are shown in

the Figures; Secure Flex components (flexible vent pipe and terminal)

may also be used.

Two 45 degree elbows may be used in place of one 90 degree elbow.

The same rise to run ratios, as shown in the venting Figures for 90

elbows,must be followed if 45 degree elbows are used.

SV4.5VF (Secure Vent), SF4.5VF (Secure Flex) firestop/spacer must

be used anytime vent pipe passes through a combustible floor or ceil-

ing. SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) firestop/spacer

must be used anytime vent pipe passes through a combustible wall.

• It is very important that the horizontal/inclined run be maintained

in a straight (no dips) and recommended to be in a slightly elevated

plane, in a direction away from the fireplace of 1/4" rise per foot (20

mm per meter) which is ideal, though rise per foot run ratios that are

smaller are acceptable all the way down to at or near level.

The tables show a 1(V) to 5(H) ratio up to a maximum horizontal run

of 20 feet except for installations where an elbow is the only vertical

vent section in the system (see Figure 35).

• AN ELBOW IS ACCEPTABLE AS 1 FOOT OF VERTICAL RISE EXCEPT

WHERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE

SYSTEM. See Figure 35.

See Table 12 as an aid in venting component selection for a particular

range of exterior wall thicknesses.

WARNING

Under no circumstances, may separate sections of

concentric flexible vent pipe be joined together.

HORIZONTAL VENT FIGURES/TABLES

Figure 36

-

Top Vent - ONE 90 DEGREE ELBOW -

ELBOW CONNECTION NOT DIRECTLY AT APPLIANCE

Example: If 20 feet of (H) hori-

zontal vent run is needed, then

4 feet minimum of (V) vertical

vent will be required.

This table shows a 1(V) to

5(H) ratio. For every 1 foot of

vertical, you are allowed 5 feet

of (H) horizontal run up to a

maximum (H) horizontal run

of 20 feet.

Venting Components Required for Various Exterior Wall Thick-

nesses, when using Square Termination Kit (SV4.5HT-2)

Vent Components Required Exterior Wall Thickness - inches (mm)
Termination Kit Only

6 to 9-1/4 (152 to 235)

Termination Kit and 6 In. Vent

Section (SV4.5L6)

10-3/4 to 14 (273 to 356)

Termination Kit and 12 in.

Vent Section (SV4.5L12)

16-3/4 to 20 (426 to 508)

Termination Kit and Tele-

scopic Section (SV4.5L12)

11-3/4 to 20 (299 to 508)

Table 12

Note: See Figure 33 showing wall thickness range

when using SV4.5HT-2 termination kit only.

Table F

H Maximum

V Minimum

feet

(meter)

feet

(meter)

3

(0.914)

Elbow Only

Table G

H Maximum

V Minimum

feet

(meter)

feet

(meter)

5

(1.524)

1

(0.305)

10

(3.048)

2

(0.610)

15

(4.572)

3

(0.914)

20

(6.096)

4

(1.219)

V + H = 40 feet (12.2 m) Max.

H = 20 ft. (6.096 m) Max.

Square termination

(SV4.5HT-2) shown.

Square termination

(SV4.5HT-2) shown.

See Table 12 as an aid in venting component selection for a particular

range of exterior wall thicknesses.

See Table 12 as an aid in venting component selection for a particular

range of exterior wall thicknesses.

See Table 12 as an aid in venting

component selection for a particular

range of exterior wall thicknesses.

Square termination

(SV4.5HT-2) shown.

Advertising