Rdvdsn series direct vent gas fireplace, Vertical through-the-roof installation – Temco Tool 39RDVDSN User Manual

Page 20

Advertising
background image

20

RDVDSN Series Direct Vent Gas Fireplace

20007894

Vertical Through-the-Roof Installation

1. Locate your fireplace.
2. Plumb to center of the (4” (102 mm) flue collar from

ceiling above and mark position.

3. Cut opening equal to 9³⁄₈” x 9³⁄₈” (240 x 240 mm).
4. Proceed to plumb for additional openings through

the roof. In all cases, the opening must provide a
minimum of 1” (25 mm) clearance to the vent pipe,
i.e., the hole must be at least 9³⁄₈” x 9³⁄₈” (240 x 240
mm).

5. Place fireplace into position.
6. Place firestop(s) #7DVFS or Attic Insulation Shield

#7DVAIS into position and secure. (Fig. 35)

7. Install roof support (Fig. 33) and roof flashing making

sure upper flange of flashing is below the shingles.
(Fig. 36)

8. Install appropriate pipe sections until the venting is

above the flashing. (Fig. 36)

9. Install storm collar and seal around the pipe.
10. Add additional vent lengths for proper height. (Fig.

37)

11. Apply high temperature sealant to 4” and 7” collars.

CFM100a

Firestop-Vertical

11"

(279mm)

11"

(279mm)

Attic Insulation
Shield

Joist

Ceiling In-
stallation

Joist

Upper Floor

Firestop Spacer

Nails (4)

CFM100a

Fig. 35 Place firestop spacer(s) and secure.

TWL101a

Twist Lock Pipe

2/8/99 djt

#8 Sheet Metal Screws

(3 per joint)

Sealant

Storm Collar

TWL101a

Fig. 36 Roof flashing.

CFM190

TTR Ternim. 2'

1/25/02 sta

CFM190

Fig. 37 Minimum termination to roof clearance.

Min. 2’ (610 mm)

If there is a room above ceiling level,
firestop spacer must be installed on both
the bottom and the top side of the ceiling
joists. If an attic is above ceiling level a
7DVAIS (Attic Insulation Shield) must be
installed.

The enlarged ends of the vent section always face
downward. (Fig. 36)