RDVDSN Series Direct Vent Gas Fireplace

20007894

T207

air shutter

setting

1/8/04 djt

T207

Fig. 49 Air shutter settings for propane/LP gas.

3/8” - All Models

Fig. 48 Replace burner orifice with correct conversion orifice.

T259

remove burner

orifice

6/04

Split Nut Assembly

Air Shutter

Burner Orifice

T259

2. Move burner tube back to original position, tighten

split nut assembly and bend tabs back up.

3. Set the air shutter opening for propane/LP gas. Tight-

en air shutter screw. (Refer to Figure 49 and Chart on
Page 31)

NOTE: Failure to adjust air shutter to proper setting

will produce sooting.

4. Fasten pilot to burner bracket with two (2) screws.
5. Replace grate assembly.

WARNING: Failure to position the parts in accor-
dance with these diagrams or failure to use only
parts specifically approved with this heater may
result in property damage or personal injury.

Valve Conversion

1. Remove plastic cap from regulator fitting. (Fig. 50)

Unscrew fitting using a 7/16” wrench. Turn fitting
over so end of fitting marked “LPG” (red) screws into
valve. Tighten fitting (snug only). Replace plastic cap.

2. Loosen screw and attach a manometer or pressure

gauge to the outlet pressure test port (1/8” NPT
plugged port) of the control valve.

3. Turn on the gas supply. Turn on the electrical sup-

ply to the appliance. Check for gas leaks using soap
and water solution or leak detection solution. Bubbles
indicate a leak that MUST be corrected. Do not use
an open flame to test for gas leaks.

4. Relight the main burners and verify proper burner

ignition and operation.

1

2

3

4

T210

White-rodgers

gas control valve

1/04 djt

T210

Regulator

Fitting

Fig. 50 White-Rodgers 25M18A-706PI gas control.

5. Check the air shutter opening for the corresponding

gas used.

6. With the main burner burning, read the pressure on

the manometer or pressure gauge. The pressure on
the gauge should read between 9.8” and 10.2” w.c.

7. Turn off the gas supply. Turn off the electrical supply

to the appliance.

8. Remove the manometer or pressure gauge. Tighten

the screw in the pressure tap.

9. Turn on the gas supply. Turn on the electrical supply

to the appliance.

10. Immediately test all gas line connections and the

control valve for gas leaks using a soap and water
solution or other gas detection solution. Bubbles in-
dicate a leak that MUST be corrected. Do not use an
open flame to test for gas leaks.

11. Using a ball point pen, fill out the conversion label

that is supplied with the conversion kit. Place the
conversion label adjacent to the rating plate.

Gas Supply Pressure (inches w.c.)

Minimum

Normal Maximum

LP (Propane)

10.8

11.0

14.0

Manifold Pressure (inches w.c.)

Normal

LP (Propane)

10.0”

Max. Input

33RDVDSP

18,000

36RDVDSP

20,000

39RDVDSP

22,000

Kit Number

33RDVDSN

36RDVDSN

39RDVDSN

Conversion Parts Included with Kit

20007864

20007891

20007903

Main Burner Orifice - LP

76776

20007908

20007907

Label, Conversion

10002876

10002876

10002876