Acceleration/deceleration time parameters, Protection parameters – Toshiba VF-S11 User Manual

Page 60

Advertising
background image

E6581160

59

7

• Acceleration/deceleration time parameters

Title

Communication

No.

Function

Unit

Minimum

setting unit

Panel/Commun

ication

Adjustment range

Default

setting

User

setting

Reference

E6581158

H

0500

Acceleration time
2

s

0.1/0.1

0.0-3200

10.0

H

0501

Deceleration time
2

s

0.1/0.1

0.0-3200

10.0

H

0502

Acceleration/decel
eration 1 pattern

-

-

0

H

0503

Acceleration/decel
eration 2 pattern

-

-

0: Linear
1: S-pattern 1
2: S-pattern 2

0

H

0504

Acceleration/decel
eration selection
(1, 2 , 3)

-

-

1: Acceleration/deceleration 1
2: Acceleration/deceleration 2
3: Acceleration/deceleration 3

1

H

0505

Acceleration/decel
eration 1 and 2
switching
frequency

Hz

0.1/0.01

0.0-WN

0.0

H

0506

S-pattern lower-
limit adjustment
amount

%

1/1

0-50

10

6.18

H

0507

S-pattern upper-
limit adjustment
amount

%

1/1

0-50

10

H

0510

Acceleration time
3

s

0.1/0.1

0.0-3200

10.0

H

0511

Deceleration time
3

s

0.1/0.1

0.0-3200

10.0

H

0512

Acceleration/decel
eration 3 pattern

-

-

0: Linear
1: S-pattern 1
2: S-pattern 2

0

H

0513

Acceleration/decel
eration 2 and 3
switching
frequency

Hz

0.1/0.01

0.0-WN

0.0

6.18

• Protection parameters

Title

Communication

No.

Function

Unit

Minimum

setting unit

Panel/Commun

ication

Adjustment range

Default

setting

User

setting

Reference

E6581158

H

0601

Stall prevention

level 1

%

(A)

1/1

10-199,

200 (disabled)

150

6.19.2

H

0602

Inverter trip
retention selection

-

-

0: Canceled with the power off
1: Still retained with the power off

0

6.19.3

H

0603

Emergency stop
selection

-

-

0: Coast stop
1: Slowdown stop

2: Emergency DC braking

0

6.19.4

H

0604

Emergency DC
braking time

s

0.1/0.1

0.0-20.0

1.0

6.19.4

H

0605

Output phase

failure detection
mode selection

-

-

0: Disabled

1: At start-up (only one time after

power is turned on)

2: At start-up (each time)

3: During operation
4: At start-up + during operation
5: Detection of cutoff on output side

0

6.19.5

H

0607

Motor 150%-
overload time limit

s

1/1

10-2400

300

6.19.1

H

0608

Input phase failure
detection mode

selection

-

-

0: Disabled, 1: Enabled

1

6.19.6