Table of input terminal functions 2

Function

No.

Code

Function

Action

34

F+SS3+AD2

Combination of forward run, preset-speed
command 3 and acceleration/deceleration 2

ON: Simultaneous input from F, SS3 and AD2

35

R+SS3+AD2

Combination of reverse run, preset-speed
command 3 and acceleration/deceleration 2

ON: Simultaneous input from R, SS3 and AD2

36

F+SS4+AD2

Combination of forward run, preset-speed
command 4 and acceleration/deceleration 2

ON: Simultaneous input from F, SS4 and AD2

37

R+SS4+AD2

Combination of reverse run, preset-speed
command 4 and acceleration/deceleration 2

ON: Simultaneous input from R, SS4 and AD2

38

FCHG

Frequency command forced switching

ON: H (If H = )
OFF: HOQF

39

VF2

No.2 Switching of V/F setting

ON: No.2 V/F setting

(RV=0, H, H, H, H)

OFF: No.1 V/F setting

(Set value of RV, XN, XNX, XD, VJT)

40

MOT2

No.2 motor switching

VF2+AD2+OCS2)

ON: No.2 motor

(RV=0, H, H, H, H,
H

, H, H, H)

OFF: No.1 motor (Set value of RV, XN, XNX,

XD

, VJT, CEE, FGE, H, H)

41

UP

Frequency UP signal input from external contacts

ON: Increase in frequency

42

DOWN

Frequency DOWN signal input from external
contacts

ON: Reduction in frequency

43

CLR

Frequency UP/DOWN cancellation signal input
from external contacts

OFF→ON: Resetting of UP/DOWN frequency by

means of external contacts

44

CLR+RES

Combination of frequency UP/DOWN cancellation
and reset by means of external contacts

ON: Simultaneous input from CLR and RES

45

EXTN

Inversion of trip stop command from external
device

OFF: G Trip stop

46

OH

Thermal trip stop signal input from external device

ON: QJ Trip stop

47

OHN

Inversion of thermal trip stop command from
external device

OFF: QJ Trip stop

48

SC/LC

Forced switching from remote to local control

Enabled when remote control is exercised
ON: Local control (setting of cmod, HOQF and
H

)

OFF: Remote control

49

HD

Operation holding (stop of 3-wire operation)

ON: F (forward run)/R: (reverse run) held, 3-wire

operation

OFF: Slowdown stop

50

CMTP

Forced switching of command mode and terminal
board command

ON: Terminal board operation
OFF: Setting of EOQF

51

CKWH

Display cancellation of the cumulative power
amount (kWh)

ON: Monitor display cancellation of the cumulative

power amount (kWh)

52

FORCE

Forced operation (factory configuration required)

ON: Forced operation mode in which operation is

not stopped in the event of the occurrence of
a soft fault (preset speed operation frequency
15) To use this function, the inverter needs to
be so configured at the factory.

OFF: Normal operation

53

FIRE

Fire-speed control

ON: Fire-speed operation (preset speed operation

frequency 15)

OFF: Normal operation

Note. When function 1, 10-12, 15-17, 38, 41-45 or 48 is assigned to an input terminal board, the input terminal

board is enabled even if the parameter command mode selection cmod is set at 1 (panel).