Caution, Warning – Tradewins Furniture RNC5-TPD User Manual

Page 19

Advertising
background image

19

It is necessary to have balanced air flow in an HRV. The vol-
ume of air brought in from the outside must equal the volume
of air exhausted by the unit. If the air flow is not properly bal-
anced, then:

• The HRV may not operate at its maximum efficiency
• A negative or positive air pressure may occur in the house
• The unit may not defrost properly
• Failure to balance HRV properly may void warranty

Excessive negative pressure

may have several undesirable

effects. In some geographic locations, soil gases such as
methane and radon gas may be drawn into the home through
basement/ground contact areas.

Read the Application Warning in Clearances & Requirements sec-
tion of this manual!

Prior to balancing, ensure that:

1. All sealing of the duct system has been completed.

2. All of the HRV’s components are in place and

functioning properly.

3. Balancing dampers are fully open.

4. Unit is on HIGH speed.

5. Air flow in branch lines to specific areas of the house

should be adjusted first prior to balancing the unit. A
smoke pencil used at the grilles is a good indicator of each
branch line's relative air flow.

6. After taking readings of both the stale air to the HRV duct

and fresh air to the house duct, the duct with the lower
CFM ([L/s] velocity) reading should be left alone, while the
duct with the higher reading should be dampered back to
match the lower reading.

7. Return unit to appropriate fan speed for normal operation

8. A field-supplied balancing damper for the stale air side

is required for system balancing.

Balancing Procedure

The following is a method of field balancing an HRV using a
Pitot tube, which is advantageous in situations when flow sta-
tions are not installed in the duct system. Procedure should
be performed with the HRV on high speed.

The first step is to operate all mechanical systems on high
speed, which have an influence on the ventilation system, i.e.
the HRV itself and the air handler, if applicable. This will pro-
vide the maximum pressure that the HRV will need to
overcome, and allow for a more accurate balance of the unit.

Drill a small hole in the duct (about 3/16"), three feet down-
stream of any elbows or bends, and one foot upstream of any
elbows or bends. These are recommended distances but the
actual installation may limit the amount of straight duct.

The Pitot tube should be connected to a magnehelic gauge or
digital manometer capable of reading from 0 to 0.25 in. (0-62
Pa) of water, preferably to 3 digits of resolution. The tube com-
ing out of the end of the Pitot is connected to the high
pressure side of the gauge. The tube coming out of the
branch of the Pitot is connected to the low pressure or refer-
ence side of the gauge.

Insert the Pitot tube into the duct; pointing the tip into the air
flow.

For general balancing it is sufficient to move the Pitot tube
around in the duct and take an average or typical reading.
Repeat this procedure in the other (supply or return) duct.
Determine which duct has the highest air flow (highest read-
ing on the gauge). Then damper that air flow back to match
the lower reading from the other duct. The flow should now be
balanced.

Actual air flow can be determined from the gauge reading.
The value read on the gauge is called the velocity pressure.
The Pitot tube comes with a chart that will give the air flow
velocity based on the velocity pressure indicated by the
gauge. This velocity will be in either feet per minute or meters
per second. To determine the actual air flow, the velocity is
multiplied by the cross sectional area of the duct being meas-
ured.

This is an example for determining the air flow in a 6" duct.

The Pitot tube reading was 0.025 inches of water.

From the chart, this is 640 feet per minute.

The 6" duct has a cross sectional area of

= [3.14 x (6"ч12)

2

]ч4

= 0.2 square feet

The air flow is then:

640 ft./min. x 0.2 square feet = 128 cfm

For your convenience, the cross sectional area of some com-
mon round duct is listed below:

DUCT DIAM. (inches)

CROSS SECTION AREA (sq.ft.)

5

0.14

6

0.20

7

0.27

The accuracy of the air flow reading will be affected by how
close to any elbows or bends the readings are taken.
Accuracy can be increased by taking an average of multiple
readings as outlined in the literature supplied with the Pitot
tube.

Ensure balanced air flow in HRV. Excessive
positive pressure may drive moist indoor air into
the external walls of the building where it may
condense (in cold weather) and degrade
structural components. May also cause key
holes to freeze up.

CAUTION

Ensure balanced air flow in HRV/ERV. Excessive
negative pressure may also cause the back-
drafting of vented combustion equipment.

WARNING

Air Flow Balancing

Advertising
This manual is related to the following products: