Caution, Warning – Tradewins Furniture RNC5-TPD User Manual

Page 9

Advertising
background image

9

Stale Air To Outside

Fresh Air From Outside

STALE AIR

from various parts of home.

i.e. bathrooms (if required), kitchens (if required).

DIRECT CONNECTION of both the HRV SUPPLY AIR STREAM and

EXHAUST AIR STREAM to the AIR HANDLER COLD AIR RETURN

Weather hood arrangement - requires a minimum
of 6' (2m) separation and a minimum of 18" (460mm)
clearance above grade or anticipated snow level.

CAUTION

It is mandatory that the air handler blower

run continuously or HRV operation be

interlocked with the air handler blower.

Check local codes/authority having

jurisdiction for acceptance.

(Return/Return Method)

NOTES:

1. Air handler blower must operate when ventilation from HRV is required.
The air handler should be set to run continuously or interlocked with HRV.
2. A minimum separation of 40 inches (1m) is required between the two direct connections.
3. The exhaust air connection should be upstream of the supply air connection to prevent
exhausting any fresh air.
4. Weather hood arrangement is for drawing purposes only. Six feet (2m) minimum separation required.
18" inches (460mm) above grade minimum or above anticipated snow level.
5. Due to the differences in pressure between the HRV and the equipment it is being
connected to, the HRV's air flow must be confirmed on site, using the balancing
procedure found in the installation manual.

HRV must be balanced.

WARNING

Air

Handler

Outdoors

*Unit is normally balanced on
HIGH speed with air handler
blower ON.

Cool Air

Return

Return Air

3' (915 mm) min.

recommended

40" (1m) MINIMUM

High efficiency filter
or electronic air cleaner

Fresh Air To Building

Application Illustrations

Simplified Installation for HRV