(3) Connecting the input signal cable

Strip the sheath from the end of each conductor of a 2-core individually shielded cable as shown in Figure
5.4. Twist those shields and cover them with a thermal contraction tube or vinyl tube not to make contact
with the case or core wires. Then attach an M3.5 crimping terminal with insulated sleeve as shown in Figure
5.3. Connect a crimping terminal to the A and B terminals on the terminal block and connect to each G
terminal of the detector and converter.

Figure 5.3 Terminal Treatment of Flow Rate Signal Cable

Notes on signal cable shield processing work

When stripping an external sheath, intermediate and insulated sheath, be careful not to scratch or cut the
internal conductors and shield mesh. Do not disjoint the shield mesh but treat it as shown in Figure 5.9.

Figure 5.4 Treating the Signal Cable Shield Mesh

M3.5 crimping terminal

Thermal contraction tube or vinyl tube

A Black

G Shield

B White

25~45mm

Shield mesh

a. Open the shield mesh with a pair of tweezers or the like.

b. Pull out the internal coated wires from the hole of the

shielded mesh.

c. Pull out all internal coated wires and extend the shield mesh

wire.

Coated wire

Separate