Toshiba Tosvert VF-AS1 User Manual

Page 46

Advertising
background image

E6581301

B-6

2

[Standard connection diagram - source]

The figure below shows an example of typical wiring in the main circuit of a 200V 0.4-45kW/400V 0.75-75kW inverter.

Main circuit power source
200V class:

0.4~45kW Three-phase

200~240V-50/60Hz

400V class:

0.75~75kW Three-phase

380~480V-50/60Hz

From (a)

Frequency

meter

Ammeter

Ammeter or voltmeter

Motor

Voltage signal:-10~+10V

Voltage signal:0~10V
or current signal:4 (0)~20mA

External potentiometer
(or voltage signal between RR/S4 and CCA:0~10V)

*5

*6

*4

*1

(a)

(a)

(a)

(a)

(a)

*7

*8

*8

*8

Forward run signal
Reverse run signal
Standby
Reset
Preset speed 1
Preset speed 2
Preset speed 3

F

a

ctory default

se

ttings

*2

*9

Main

circuit

*3

Noise

filter

Control

circuit

*9, *10

*1: The inverter is shipped with the terminals PO and PA/+ shorted with a bar (200V-45kW or smaller, 400V-75kW or smaller).

Remove this shorting bar when installing a DC reactor (DCL).

*2: The DC reactor is built in for models 200V-11kW~45kW and 400V-18.5kW~75kW.

*3: The noise filter is built in for models 200V-45kW or smaller and all of 400V.

*4: External braking resistor (option). Dynamic braking drive circuit built-in (GTR7) as standard for models 160kW or smaller.

*5: To supply a DC power, connect the cables to the PA/+ and PC/- terminals.

*6: If you want to use a DC power supply to operate the inverter (200V: 18.5kW or more, 400V: 22kW or more), be sure to

contact your supplier customer support center, because an inrush current limiting circuit is required in such a case.

*7: Refer to Section 2.3.2 for chip switch functions.

*8: The functions assigned to terminals OUT1, VI/VII and RR/S4 can be switched by changing parameter settings. For details

refer to Section 2.3.2.

*9: To supply control power from an external power supply for backing up the control power supplied from the inverter, an

optional control power backup device (CPS002Z) is required. In such a case, the backup device is used at the same time

with the internal power supply of the inverter.

*10: The optional control power backup unit can be used with both 200V and 400V models.