E6581301

E-24

5

3) Inverter overload characteristics

Set to protect the inverter unit. Cannot be turned off by parameter setting.
The inverter has two overload detecting functions, which can be switched from one to another using parameter
H

(inverter overload detection mode selection).

[Parameter setting]

Title

Function

Adjustment range

Default setting

H

Inverter overload selection



:Standard (150 -60 sec.)



:

Estimation of temperature



If the inverter overload trip function (QN) is activated frequently, this can be improved by adjusting the stall
operation level H downward or increasing the acceleration time CEE or deceleration time FGE.

H= (Standard)

Protection is given uniformly regardless of ambient temperature, as shown by the 150%-60 sec overload curve in
the figure below.

60

100%: Inverter rated output current

time [s]

Inverter overload

Monitored output current [%]

0

110%

150%

Current

[%]

Inverter overload time [s]

(Outline data)

111

2400

120

240

130

120

140

80

150

60

165

2

200

0.1

Inverter overload protection characteristics

H= (Estimation of temperature)

This parameter adjusts automatically overload protection, predicting the inverter internal temperature rise.
(diagonally shaded area in the figure below)

60

100%: Inverter rated output current

time [s]

Monitored output current [%]

0

110%

150%

Inverter overload protection characteristics

Note 1: If the load applied to the inverter exceeds 150% of its rated load or the operation frequency is less than

0.1Hz, the inverter may trip in a shorter time.

Note 2: The inverter is factory-set so that, if the inverter becomes overloaded, it will automatically reduce the

carrier frequency to avoid an overload trip. A reduction in carrier frequency causes an increase in noise
from the motor, but this does not affect the performance of the inverter.
If you do not want the inverter to reduce the carrier frequency automatically, set the parameter
H

=.