Listed below are the default settings of the primary UPS parameters.

Settings Options

Default

Remarks

1) O/P VOLT SET
(output voltage
set)

100V/110V/115V/120V/127V
208/220/230/240 Vac

120V
230V

120V (FOR LV series)
230V (FOR HV series)

2) I/P FREQ SET
(input frequency
setting)

+/- 2%
+/- 5%
+/- 7%

+/- 5%

Input Frequency range in
Free Run mode

3) I/P BYPASS
SET
(input bypass
setting)

+/- 10%
+10% -15%
+15% -20%

+10%
-15%

Input Voltage range when
Bypass mode is on

4) FREE RUN
SET

ON/OFF

ON

If ON, enable UPS runs on
Asynchronous mode.
For example:
If input freq 55Hz
output freq stays at 60Hz.

If OFF, disable UPS runs on
synchronous mode.
For example:
If input freq 55Hz,
UPS will go to battery mode.

5) HE MODE SET

ON/OFF

OFF

If ON, enable UPS runs in
High efficiency mode. The
unit will be in bypass mode
with 95% or higher
efficiency.

If OFF, the unit will be in the
online mode with 85%
efficiency.

6) MANUAL
BYPASS

ON/OFF

OFF

If ON, enable UPS switch to
Bypass mode immediately.