16

port cannot be used when using the USB port. The USB cable is a standard cable and

may be purchased separately.

5.4

EPO Port (emergency power off)

A customer-supplied switch located remotely may be used to open the EPO connection

and force the UPS output receptacles to be switched off. The EPO function shuts down

the equipment immediately. An EPO will not provide an orderly shutdown. The UPS

will have to be manually restarted in order to regain power to the outlets.

After an Emergency Power Off (EPO), do not reset the breaker until the UPS has been

fully discharged. The UPS could be damaged if the unit is not fully discharged before

the breaker is reset.

5.5

Network Transient Protector

The network transient protector, located on the back panel, has both IN and OUT RJ45

10 baseT jacks and will protect a single network connector. Connect the input connector

to the jack labeled IN, and the output connector to the jack labeled OUT.

5.6 Load

Segments

The sets of receptacles known as load segments provide organized shutdown and

startup of the equipment. Less critical equipment can be turned off during power

outages saving battery power for critical loads. The load group status can be viewed

from the LCD display and can be changed if necessary.

Load 10% 20% 30% 40% 50% 60% 70% 80%

90%

100%

1000VA

Backup

(min) 150

56 38 30 23 19 15 12 10 7

1500VA

Backup

(min) 80 37 21 19 18 15 13 11 8 6

2000VA

Backup

(min) 150

68 38 26 19 14 11 9 8 7

3000VA

Backup

(min) 80 40 25 19 15 12 9 8 7 6