27

LIMITATIONS AND EXCLUSIONS

1.

This limited warranty shall not cover the UPS, UPS parts, or BATTERY during their
respective warranty periods, if the following storage, maintenance, installation, operating
conditions are not met throughout the warranty periods (5 conditions below):

Valve Regulated Lead Acid (VRLA) Batteries for Toshiba UPS Required Operating, Installation, and

Maintenance Conditions

1. Temperature

Annual Average Temperature is to be 77

°F (25°C) with no greater

temperature of 89

°F (32°C) for more than 30 days

Maximum Number of Cycles (24 Months)***

Discharge Time

Battery > 9AHr

Battery < 9AHr

30 min

20

69

15 min

25

86

10 min

32

110

5 min

38

130

2. Maximum # of Full
Charge/Discharge
Cycles

*** > 9AHr Typically extended runtimes < 9AHr Typically Single Phase
Systems.

3. Storage

While UPS is in Transit or in storage, it must always be in a suitable
temperature (as stated above)

4. External Battery

Parallel battery string applications must be approved by TIC in writing

5. Idle Batteries

User must recharge the batteries if not in use (charged) for more than 6
months

Credit for Replacement Battery When Approved Warranty

Time from Shipments

UPS Batteries

Cost to Customer

Months

% Credit

% List Price

0-24 100

0

25-30 55

45

31-36 45

55

37-42 35

65

43-48 25

75

49-54 15

85

55-60 5

95