Limit control, Cont’d), Pressure switch settings – Thomas & Betts UDAP User Manual

Page 18

Advertising
background image

Form RZ-NA I-UDA, P/N 195673 Rev 5, Page 18

18. Flame

Rollout
Switch -
Sizes 30-125
only

16. Combustion

Air Proving
Switch

(cont’d)

Sizes 30-125 are equipped with a temperature activated manually reset flame rollout
switch. The flame rollout switch is located at the top of the burner assembly. It is
factory set and is non-adjustable. If the setpoint is reached, the flame rollout acts to
interrupt the electric supply to the gas valve. If the flame rollout switch activates,
identify and correct the cause before resetting the switch. Refer to the Mainte-
nance Section for information on probable causes and instructions on resetting the
flame rollout switch. (For location, see FIGURE 18, page 31.)

DANGER: If the manual reset flame rollout switch activates,
identify and correct the cause before resetting the switch. Never
bypass the flame rollout switch; hazardous conditions could result.
See Hazard Intensity Levels, page 2.

17. Limit Control

All units are equipped with a temperature activated auto reset limit control. The
control is factory set and is non-adjustable. If the setpoint is reached, the limit
control will interrupt the electric supply to the gas valve. This safety device pro-
vides protection in the case of motor failure or lack of airflow due to a restriction at
the inlet or outlet. (For location, see FIGURE 18, page 31.)

CAUTION: The auto reset limit control will continue to shut down
the heater until the cause is corrected. Never bypass the limit
control; hazardous conditions could result. See Hazard Intensity
Levels, page 2.

The two Tables on the left below list the approximate water column negative pres-
sure readings and switch setpoints for sea level operating conditions for Model
UDAP and Model UDAP-CV heaters. The Table on the right lists the approximate
water column differential pressure readings and switch setpoints for sea level op-
erating conditions for Model UDAS heaters.

Pressure Switch Settings

DANGER: Safe operation of this unit requires proper venting
flow. NEVER bypass combustion air proving switch or attempt
to operate the unit without the venter running and the proper
flow in the vent system. Hazardous conditions could result. See
Hazard Levels, page 2.

Startup Equilibrium

Setpoint

Setpoint

Startup Equilibrium Setpoint Setpoint

Cold

Hot

OFF

ON

Cold

Hot

OFF

ON

30

1.00

0.78

0.40

0.58

Green

197030

30

1.00

0.78

0.65

0.83

Yellow 197028

45

0.95

0.75

0.40

0.58

Green

197030

45

1.05

0.80

0.65

0.83

Yellow 197028

60

1.00

0.78

0.50

0.68

Orange 196388

60

1.10

0.85

0.65

0.83

Yellow 197028

75

1.00

0.85

0.50

0.68

Orange 196388

75

1.10

0.85

0.65

0.83

Yellow 197028

100

0.85

0.72

0.50

0.68

Orange 196388

100

0.85

0.72

0.55

0.73

White 196362

125

0.75

0.60

0.40

0.58

Green

197030

125

0.75

0.60

0.45

0.63

Pink

197032

150, 175

0.75

0.65

0.40

0.58

Green

197030

150, 175

0.75

0.60

0.40

0.58

Green 197030

200, 225

2.20

1.50

1.10

1.30

Blue

201158

200, 225

2.20

1.50

1.10

1.30

Blue

201158

250, 300

2.30

1.60

1.10

1.30

Blue

201158

250, 300

2.30

1.60

1.10

1.30

Blue

201158

350, 400

2.60

1.80

1.40

1.60

Red

201159

350, 400

2.60

1.80

1.40

1.60

Red

201159

Startup

Equilibrium Setpoint Setpoint

Cold

Hot

OFF

ON

1.10

0.84

0.65

0.83

Yellow

1.10

0.81

0.50

0.68

Orange

0.92

0.75

0.60

0.78

Lt Blue

0.97

0.78

0.60

0.78

Lt Blue

0.88

0.71

0.55

0.73

White

100

Switch

P/N

197028
196388
197029
197029
196362

30
45
60
75

Differential Pressure Measured in " w.c.

Model

UDAS

Label
Color

Switch

P/N

Negative Pressure Measured in " w.c.

Label
Color

Switch

P/N

Model

UDAP

Label
Color

Negative Pressure Measured in " w.c.

Model UDAP-CV

with Opt AV6