Burner maintenance, Heat exchanger maintenance, Burner removal instructions (refer to figure 17.) – Thomas & Betts UDAP User Manual

Page 29: Caution: use of eye protection is recommended

Advertising
background image

Form RZ-NA I-UDA, Mfg #195673 Rev 5, Page 29

27. Burner

Maintenance

This heater is equipped with a

T

CORE

2

®

burner (patent pending).

Inspect the burner/control compartment annually to determine if cleaning is nec-
essary. If there is an accumulation of dirt, dust, and/or lint, clean the compartment
and follow the instructions below to remove and clean the burner.

CAUTION: Use of eye protection is recommended.

1. Outside the cabinet, shut the gas supply off at the manual valve ahead of the

union.

2. Turn off electric supply.
3. Disconnect the gas supply at the union outside of the cabinet.
4. Remove the access panel.
5. Disconnect the Gas Train and Move Out of the Way - At the gas valve,

mark and disconnect the wires. Carefully remove the burner orifice and
orifice adapter locking nut. Slide the orifice adapter out through the bracket
on the burner pushing the gas train to the right. This will move the gas train
out of the way.

6. Move the Control Assembly - Remove the two screws holding the control

assembly bracket. Being careful not to disconnect any wires, slide the control
assembly to the right.

7. Remove Secondary Air Baffles (Sizes 60-400 only) - Vertical along the right

side of the burner, locate the flat plate(s) identified as the secondary air
baffle(s). The quantity of baffles could be one to four depending on heater

26. Heat

Exchanger
Maintenance

This heater is equipped with a

T

CORE

2

®

heat exchanger (patent pending).

Remove any external dirt or dust accumulation. Visually check the heat exchanger
for cracks and holes. If a crack or hole is observed, replace the heat exchanger.

NOTE: Inspection of the lower portion of the heat exchanger is done with the
burner removed. See the Burner Service section below for information on inspect-
ing the lower portion of the heat exchanger.

Burner Removal
Instructions (Refer
to FIGURE 17.)

FIGURE 17 - Burner
Removal (UDAP
illustrated; same process
for both UDAP and UDAS)

Venturi Tube

Orifice Adapter Locking Nut

Slide right; rotate

inward; pull out

Gas Valve

Burner

Orifice

Burner

Assembly

Secondary Air Baffle

(Qty varies per size.)

Mark locations before removing.

Control Bracket Screws -

Loosen bracket; slide right.

Slide Right

Secondary Air Shield

Burner Body Support (at least two per unit) - Remove screw attaching

to secondary air shield. Support remains attached to burner.

Disconnect gas train at

orifice and outside the

heater; slide to the right.

Advertising