Step 2: cabinet preparation, Caution, Note – Thermador PRL36 User Manual

Page 6

Advertising
background image

English 4

Step 2: Cabinet Preparation

1.

The range is a free standing unit. If the unit is to be
placed adjacent to cabinets, the clearances shown in
Figure 1 are required. The same clearances apply to
island installations, except for the overhead cabinets,
which must have a space wide enough to accept the
flared island hood, as indicated in Figure 1.

2.

These ranges may be recessed into the cabinets
beyond the edge of the front face of the oven (See
Figure 2).

3.

The gas and electrical supply should be within the zone
shown in Figure 3a.

CAUTION:

In these installations, the door and cabinet can
cause a pinching hazard.

Note:
The maximum depth of over head cabinets installed on
either side of the hood is 13" (330 mm).

A 36-inch minimum clearance is required between the top
of the cooking surface and the bottom of an unprotected
cabinet. A 30-inch clearance can be used when the bottom
of the wood or metal cabinet is protected by not less than

1/4 inch of a flame retardant material covered with not less
than No. 28 MSG sheet steel, 0.015 inch (0.4 mm) thick
stainless steel, 0.024 inch (0.6 mm) aluminum, or 0.020
inch (0.5 mm) thick copper.

Flame retardant materials bear the mark:

UNDERWRITERS LABORATORIES INC.
CLASSIFIED MINERAL AND FIBER BOARDS
SURFACE BURNING CHARACTERISTICS

Followed by the flame spread and smoke ratings. These
designations are shown as “FHC (FIame Spread/Smoke
Developed)”. Materials with “O” flame spread ratings are
flame retardant. Local codes may allow other flame spread
ratings.

4.

Any openings in the wall behind the range and in the
floor under the range must be sealed.

5.

When there is less than a 12" horizontal clearance

between combustible material

Δ

and the back edge of

the range above the cooking surface, a Thermador
Low Back or Pot and Pan Shelf must be installed. (See

Figure 2). When clearance to combustible material

Δ

is over 12", a Thermador Flush Island Trim may be
used. Figure 2 indicates the space required for each
type of backguard.

6.

Always keep appliance area clear and free from
combustible materials, gasoline and other flammable
vapors and liquids.

7.

Do not obstruct the flow of combustion and ventilation
air to the unit.

8.

A 5 inch minimum clearance is needed when the range
is installed beside a combustible side wall.

Δ

A

s defined in the “National Fuel Gas Code” (ANSI

Z223.1, NFPA 54 Current Edition).

Advertising
This manual is related to the following products: