Controls – Venmar HEPA 3100* User Manual

Page 18

Advertising
background image

6.1 M

AIN

S

WITCH

All units are equipped with a 3-position main switch, located on the front panel.

6.2 40415

AND

40425 W

ALL

C

ONTROLS

D

ESCRIPTION

The included wall control is 40415 (intented for HRV 2600, HEPA 3100 and HEPA 4100 units only) or 40425 control (intented for
HR 2.6 and HF 3.1 units only). The wall control is in OFF mode when power is applied for the first time. The mode does not change
following a power failure.

40415

CONTROL OR

40425

CONTROL

6.3 O

PERATING

40415 / 40425 C

ONTROLS

The wall controls 40415 and 40425 provide 5 operation modes. Press the Mode button to select the desired mode.

6. CONTROLS

OFF:

U

NIT IS OFF AND

DOOR IS

UNLOCKED

.

NORMAL/REMOTE:
U

NIT IS OPERATING ON

NORMAL SPEED

. T

HIS IS

THE RIGHT POSITION

WHEN A WALL CONTROL

IS USED

.

BOOST:

U

NIT IS OPERATING

ON HIGH SPEED

.

VC0098

VC0053

- 18 -

I

LLUMINATES IN ALL MODES

EXCEPT

OFF

MODE

.

F

ILTER AND PREFILTER MAINTENANCE

LED.

F

LASHES WHEN IT IS TIME TO REPLACE

PREFILTER AND WASH CORE FILTERS

.

S

EE

B

IANNUAL

M

AINTENANCE IN

S

ECTION

7.1.

L

IGHTS UP WHEN IT IS TIME TO REPLACE

FILTER AND PREFILTER AND WASH CORE FILTERS

.

S

EE

A

NNUAL

M

AINTENANCE

S

ECTION

7.2.

The unit exchanges air

at normal speed.

The outdoor

temperature* is displayed.

The unit exchanges air

at high speed.

The outdoor

temperature* is displayed.

The unit recirculates air. However,

every 20 minutes the unit

exchanges air for

2.5 minutes so that it can obtain

a reading of the outdoor temperature*.

The unit operates on a 60-minute cycle.

For the first 40 minutes, the unit recirculates

air or is off (See configuration parameter 2).

For the last 20 minutes, it exchanges air.

However, if the outdoor temperature* is too

high or too low (see configuration

parameters 3 and 4), the unit recirculates

air during the last 20 minutes.

N

ORMAL

M

ODE

(M

IN

)

B

OOST

M

ODE

(M

AX

)

R

ECIRCULATION

M

ODE

(R

E

-

CIRC

)

O

FF

M

ODE

The unit is off.

The outdoor temperature*

is not displayed.

Off in

Auto mode

Air exchange in

Auto mode

Air recirculation

in Auto mode

A

UTOMATIC

M

ODE

(A

UTO

)

P

RESS THIS BUTTON TO

ACCESS CONFIGURATION PARAMETERS

(

SEE SECTION

6.4).

• P

RESS EITHER BUTTON TO CHANGE

CONFIGURATION SETTING

(

SEE SECTION

6.4).

• P

RESS BOTH BUTTONS TO RESET THE FILTER

COUNTER OR PREFILTER COUNTER

.

P

RESS THIS BUTTON TO

SWITCH MODE

(

SEE

S

ECTION

6.3).

* The outdoor temperature reading is taken from the unit

FRESH AIR

FROM OUTSIDE port; due to the lenght of the insulated duct, the reading
is slightly different from the real outside temperature.