Operation and Description of Instrument Function

Average Temperature/Water Bottom Sensor and Converter

36

Installation and Operations Manual

VH48 Gas Offset
Item type: read and write
Default: 300mm
Range: 0mm ~ 99999mm
A function to exclude specific element(s) from the gas (vapor) phase average

temperature calculation when the uncovered element(s) is (are) within the entered value

from the liquid level.

VH49 Liquid Offset
Item type: read and write
Default: 300mm
Range: 0mm ~ 99999mm
A function to exclude element (s) from the liquid phase average temperature calculation

when the uncovered element(s) is (are) within the entered value from the liquid level.

Liquid Level

Liquid phase

Gas phase

VH48 GAS Offset

300mm (default)

Temp. element within this range will be

excluded from Gas average calculation

To 4532 ATC Electric housing

Temperature
Element

To Tank floor

Liquid Level

Liquid phase

Gas phase

VH49 Liquid Offset:

300mm (default)

Temp. element within this range will be

excluded fr om liquid average calculation

To Tank floor

Temperature

Element

To 4532 ATC Electric housing