Venting installation, Continued – Vanguard Heating VDVF36PP User Manual

Page 10

Advertising
background image

10

105706

DIRECT-VENT GAS FIREPLACE HEATER

VDVF36P and VDVF36ST Series

®

VENTING
INSTALLATION

Continued

UP

Figure 21 - Horizontal Termination Configuration for Rigid Venting Using One
90

°

Elbow

Figure 22 - Horizontal Termination Using Flexible Venting

Horizontal Venting

Vertical (V)

Horizontal (H)

49.5" min.

15" max.

(45

°

elbow, 1' vertical pipe, 90

°

elbow)

61.5" min.

34" max.

73.5" min.

58" max.

85.5" min.

10' max.

102.5" min.

20' max.

UP

Horizontal Venting

See information in
Figure 21 for
Vertical(V) and
Horizontal(H) maxi-
mums and minimums.
The same amounts
apply for flexible
venting.

FGFVK Vent Kit Shown

Horizontal Termination
Configurations

Figures 21 through 23 show different con-
figurations for venting with horizontal ter-
mination. Each figure includes a chart with
vertical minimum/maximum and horizon-
tal maximum dimensions which must be
met. All connections must be sealed with
high temperature silicone sealant as speci-
fied in the second warning statement on
page 7. All horizontal terminations require
1/4" rise per 12" of horizontal run.

Note: The 30

°

Starter

Elbow Must Be
Discarded and
Replaced with a 45

°

Starter Elbow.

45

°

Starter

Elbow
Required