Installation, Clearances to combustibles, Materials required – Waterford Appliances NATURAL GAS E61-LP User Manual

Page 7

Advertising
background image

7

Waterford E61 Gas Fireplace Insert

CLEARANCES TO

COMBUSTIBLES

The following clearances to combustibles must
be observed:

From Unit

Sides

A

9" / 229 mm

Unit to Unprotected Mantel B

16" / 406 mm

Unit to Protected Mantel*

B

12" / 305mm

*Mantel shield must have a 1" (25mm) air space
between the mantel and shield and a 1" (25mm)
gap between on the back of the shield and the
facing.

In addition to these clearances, adequate ac-
cessibility clearance for servicing and proper
operation must be maintained.

Do not in any way obstruct the air inlets that are
located on the front of the heater.

Combustible Mantels are permitted within the
shaded area.

Combustibles are permitted within
the shaded area, on either side.

5) Pull the vent connector plate through the

tapered brackets and fasten to the front
plate. See page 9.

6) Slide the unit fully into the fireplace and

level.

7) Test gas pressure, page 11. Check aera-

tion, page 12.

8) Assemble and install the shroud. See page

12.

9) Install Optional Door Grill. See page 13.

10) Install the log set. See page 13.

11) Install Optional Remote Control, and Op-

tional Wall Thermostat, if required. See
pages 13 and 14.

12) Explain controls to the homeowner.

15) Final check: Before leaving this unit with

the customer, the installer must ensure that
the appliance is firing correctly. This in-
cludes:

a) Clocking the appliance to ensure the

correct firing rate.

b) Adjusting the primary air, if required, to

ensure that the flame does not carbon.
See page 12.

c) Ensuring that the appliance is venting

correctly.

MATERIALS

REQUIRED

No electrical power supply is required for the
gas control to operate. A 120 Volt AC power
cord is hooked up to the fan switch and blower.
Plug 3 wire cord into a suitable receptacle. Do
not cut the ground terminal off under any
circumstances.

When connected with 120 volts, the appliance
must be electrically grounded in accordance
with local codes, with a current version of CSA
C22.1 (in Canada) or in the absence of local
codes, with the National Electrical Code ANSI/
NFPA 70-1987.

Note: This unit is equipped with a heat

sensor thermodisc which will
prevent the blower from operat-
ing until the unit reaches the cor-
rect temperature.

INSTALLATION

WARNING:

Electrical Grounding Instructions

This appliance is equipped with a
three pronged (grounding) plug
for your protection against shock
hazard and should be plugged
directly into a properly grounded
three-prong receptacle. Do not cut
or remove the grounding prong
from this plug.

Floor Protection

An approved floor protector is required con-
sisting of a layer of 1/2" (13mm) Wonderboard
(or Durock or equivalent) that extends 9"
(229mm) in front of the fireplace measured at
the base (this equals 16" from the fireplace
opening), and as wide as the appliance.

Note: If the appliance is installed in a

fireplace that is elevated 5"
(127mm) or higher (i.e., a Water-
ford Zero Clearance Cabinet, zero
clearance fireplace, brick plinth,
etc.), no floor protection is re-
quired in front of the appliance.

When the Insert is installed in a fireplace that is
elevated 5" or higher, no floor protection is
required in front of the appliance.