Installation

FIG. 11

Questions? Visit www.yukon-eagle.com or call 1-800-358-0060

DRAW COLLAR (Models LWO-168 & LWG-168 ONLY)
Firmly attach the draw collar around the stainless steel
smoke pipe. Keep the field installed smoke pipe at least 2 "
away from draw collar. This will insure that smoke leaving
the furnace will not be drawn into the circulating air stream.
See Fig. 11.

NOTE: Only Models LWO-168 and LWG-168 are

equipped with a draw collar.

NOTE: If barometric damper control is installed

horizontally as illustrated, it must be at least 8
inches from furnace smoke outlet.

DAMPER CONTROL

NOTE: Refer to the wiring diagrams in the back of

manual in “Exploded Views and Parts List.”

Remove control from accessory box and install as
follows:

1. Remove the four screws that hold the gasket to the

DS-103 panel.

2. Mount the DS-103 to the draft tube using screws

removed above. Make sure gasket stays in place.
See Fig. 12

3. Loosen the two screws located at slotted end of

draft tube, and remove remaining 10 screws. Make
sure gasket stays in place.

4. Mount DS-103 control and draft tube assembly to

furnace as shown. See Fig. 12

5. The electrical connections will be completed later in

the Installation Instructions.

FIG. 12

Draft Tube
Assembly

Damper Control

CHIMNEY

DRAFT

REGULATOR

DRAW

COLLAR FILTER

DOOR

SMOKE