FURNACE LOCATED IN CONFINED SPACE

When the furnace is in utility room, install two open grilles.

(

See Fig. 28.) Place them in a wall or door opening to the

rest of the house. One grille will supply combustion air.
Locate it near the floor. The other grille is for ventilation.
Locate it close to the ceiling. Each grille must have a free
area. It should be not less than one square inch for each
1000 BTU/hr. of the total input rating of appliances in
confined space.

FOR EXAMPLE: Your furnace is rated at 150,000 BTU
per hour. The water heater is rated 30,000 BTU per hour.
The total is 180,000 BTU per hour. You need two grilles,
each with 180 square inches of free opening. Metal grilles
have about 60% free (open) area. Therefore, you need
two metal grilles with 300 square inches each of louvered
area. The height should be about half the width.

FIG. 28

SIZE

1/4” MESH

SCREEN

BTU

WOOD

LOUVERS

BTU

METAL

LOUVERS

BTU

3-1/4 X 12 INCH

8 INCH ROUND

8 X 12 INCH

8 X 16 INCH

144,000

200,000

382,000

512,000

36,000

50,000

96,000

128,000

108,000

150,000

288,000

384,000

BTU Per Hour Input*

* Based on opening covered by 1/4 inch mesh screen, wood or metal louvers.

FRESH AIR DUCT CAPACITIES