TABLE 7 - SUPPLY AIR BLOWER PERFORMANCE (20 TON)

BLOWER

SPEED,

(RPM)

MOTOR

PULLEY
(TURNS

OPEN)*

CFM

6000

7000

8000

9000

9400

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

208 VOLT AND STANDARD DRIVE

870

6.0**

0.4

2.1

1.8

0.1

2.3

2.0

-

-

-

-

-

-

-

-

-

900

5.0

0.8

3.2

2.7

0.5

3.5

2.9

0.2

3.8

3.2

-

-

-

-

-

-

930

4.0

1.1

4.1

3.4

0.9

4.5

3.8

0.6

4.9

4.1

0.1

5.1

4.3

-

-

-

950

3.0

1.3

4.6

3.9

1.1

5.1

4.3

0.8

5.5

4.6

0.4

5.9

5.0

-

-

-

980

2.0

1.6

5.3

4.5

1.4

5.8

4.9

1.2

6.3

5.3

0.7

6.9

5.8

0.2

7.3

6.1

1015

1.0

1.9

5.9

5.0

1.7

6.5

5.5

1.5

7.0

5.9

1.0

7.7

6.5

0.6

8.2

6.9

208 VOLT AND HIGH SPEED DRIVE ACCESSORY

950

6.0

1.3

4.6

3.9

1.1

5.1

4.3

0.8

5.5

4.6

0.4

5.9

5.0

-

-

-

980

5.0

1.6

5.3

4.5

1.4

5.8

4.9

1.2

6.3

5.3

0.7

6.9

5.8

0.2

7.3

6.1

1010

4.0

1.8

5.8

4.9

1.7

6.3

5.3

1.5

6.9

5.8

1.0

7.5

6.3

0.5

7.9

6.7

1020

3.5

1.9

6.1

5.1

1.8

6.5

5.5

1.6

7.1

6.0

1.1

7.8

6.6

0.6

8.3

7.0

1035

3.0

2.0

6.2

5.2

1.9

6.8

5.7

1.7

7.4

6.2

1.2

8.1

6.8

0.7

8.6

7.3

1050

2.5

2.1

6.4

5.4

2.0

7.0

5.9

1.8

7.6

6.4

1.3

8.3

7.0

-

-

-

1075

2.0

2.3

6.6

5.5

2.1

7.2

6.0

1.9

7.8

6.6

1.5

8.6

7.2

-

-

-

1100

1.0

2.4

6.7

5.6

2.2

7.3

6.1

2.1

7.9

6.7

-

-

-

-

-

-

230/460/575 VOLT AND STANDARD DRIVE

870

6.0**

0.4

2.1

1.8

0.1

2.3

2.0

-

-

-

-

-

-

-

-

-

900

5.0

0.8

3.2

2.7

0.5

3.5

2.9

0.2

3.8

3.2

-

-

-

-

-

-

930

4.0

1.1

4.1

3.4

0.9

4.5

3.8

0.6

4.9

4.1

0.1

5.1

4.3

-

-

-

950

3.5

1.3

4.6

3.9

1.1

5.1

4.3

0.8

5.5

4.6

0.4

5.9

5.0

-

-

-

980

2.5

1.6

5.3

4.5

1.4

5.8

4.9

1.2

6.3

5.3

0.7

6.9

5.8

0.2

7.3

6.1

1015

1.5

1.9

5.9

5.0

1.7

6.5

5.5

1.5

7.0

5.9

1.0

7.7

6.5

0.6

8.2

6.9

1025

1.0

2.0

6.1

5.1

1.8

6.6

5.6

1.6

7.3

6.1

1.1

7.9

6.7

0.7

8.6

7.3

230/460/575 VOLT AND HIGH SPEED DRIVE ACCESSORY

950

6.0

1.3

4.6

3.9

1.1

5.1

4.3

0.8

5.5

4.6

0.4

5.9

5.0

-

-

-

980

5.0

1.6

5.3

4.5

1.4

5.8

4.9

1.2

6.3

5.3

0.7

6.9

5.8

0.2

7.3

6.1

1015

4.0

1.9

5.9

5.0

1.7

6.5

5.5

1.5

7.0

5.9

1.0

7.7

6.5

0.6

8.2

6.9

1035

3.5

2.0

6.2

5.2

1.9

6.8

5.7

1.7

7.4

6.2

1.2

8.1

6.8

0.7

8.6

7.3

1050

3.0

2.1

6.4

5.4

2.0

7.0

5.9

1.8

7.6

6.4

1.3

8.3

7.0

-

-

-

1080

2.0

2.3

6.6

5.5

2.1

7.2

6.0

1.9

7.8

6.6

1.5

8.6

7.2

-

-

-

1100

1.5

2.4

6.7

5.6

2.2

7.3

6.1

2.1

7.9

6.7

-

-

-

-

-

-

1120

1.0

2.5

6.8

5.7

2.3

7.4

6.2

2.2

8.1

6.8

-

-

-

-

-

-

NOTES: 1. Blower performance includes fixed outdoor air, 2" T/A filters, a dry indoor coil and no electric heat.

2. Refer to Page 12 for additional static resistances.

ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted
from the total static pressure of the blower.

*

Do

NOT close the pulley below 1 turn open.

** Factory setting.

240 MBH - BOTTOM DUCT CONNECTIONS