York SUNLINE 2000 B1CH240 User Manual

Page 8

Advertising
background image

TABLE 4 - PHYSICAL DATA

MODELS

UNIT SIZE

15 TON 20 TON

SUPPLY AIR

BLOWER

CENTRIFUGAL BLOWER (Dia. x Wd. in.)

15 x 15 18 x 15

FAN MOTOR HP

5

7.5

INDOOR

COIL

ROWS DEEP

4

4

FINS PER INCH

13

13

FACE AREA (Sq. Ft.)

15.5

20.5

OUTDOOR

FANS

(Two Per Unit)

PROPELLER DIA. (in.) (Each)

30

30

FAN MOTOR HP (Each)

1

1

NOM. CFM TOTAL (Each)

6500

7200

OUTDOOR

COILS

ROWS DEEP

3

3

FINS PER INCH

15

15

FACE AREA (Sq. Ft.)

36.0

43.3

COMPRESSOR

(Qty. Per Unit)

7-1/2 TON TANDEM

2

-

10 TON TANDEM

-

2

AIR

FILTERS

QUANTITY PER UNIT (16" X 20" X 2")

-

4

QUANTITY PER UNIT (16" X 25" X 2")

-

4

QUANTITY PER UNIT (18" X 24" X 2")

5

-

TOTAL FACE AREA (sq. ft.)

15.0

20.0

CHARGE

REFRIGERANT 22

(lbs./oz.)

SYSTEM NO. 1

20/8

24/0

SYSTEM NO. 2

22/8

25/0

OPERATING WEIGHTS (LBS.)

15 TON

20 TON

Basic Unit

Heat Pump

2000

2200

Options

Economizer

160

Economizer with
Power Exhaust

245

Motorized Damper

150

Electric Heat
(Nominal KW)

18 KW

25

36 KW

30

54 KW

35

72 KW

40

Accessories

Roof Curb

175

185

Barometric Damper

45

45

Wood Skid

200

220

511.06-N3Y

8

Unitary Products Group